Hayward Heaters
Refer to the instructions in the heater manual for
1.Turn off power to heater
2.WireAqua Logic to terminals 1 & 2 (see diagram)
3.Leave jumper attached to terminals 4 & 5
4.Move “BYPASS” dipswitch on heater circuit board to “ON” position (up)
5.Turn heater power back on
6.Switch heater to either “Pool” or “Spa” (it doesn’t make any difference which is selected, the Aqua Logic will take control)
7.Heater display should be “bO” (for “bypass On)
8.Heater will fire wheneverAqua Logic requests (whenAqua Logic “Heater” LED is illuminated)
ºC ON
ºF OFF
Dipswitch located on heater circuit board
PK
W
R
BK
R
Pool/Spa |
Air |
Solar |
Heater1 |
Heater2 |
Do not remove jumper
Terminal block located at electrical junction box
Pentair/Purex/MiniMax
1.Turn power off to heater
2.Remove factory installed jumper from the “Ext Switch” connector.
3.Wire theAqua Logic to the “Ext Switch” connector as shown below
4.The wires to the Aqua Logic must be separated from any line voltage wires. Failure to follow these instructions may cause erratic operation of the heater.
5.Set the Power (Thermostat Select) switch to either “Pool” or “Spa”
6.Set the “Pool” and “Spa” thermostats to their maximum settings.
Remove
Factory Jumper
Ext.
Switch
MINIMAX
Pool/Spa |
Air |
Solar |
Heater1 |
Heater2 |
15 |