Grounding and Bonding
Connect a ground wire from the primary electrical panel to theAqua Logic ground bus bar. Also ground each piece of high voltage (120 or 240VAC) equipment that is connected to theAqua Logic control relays or circuit breakers.
TheAqua Logic should also be connected to the pool bonding system by an 8AWG (6AWG for Canada) wire. Alug for bonding (2 for Canada) is provided on the outside/bottom of theAqua Logic enclosure.
Circuit Breaker Installation and Wiring
Circuit breakers are to supplied by the installer. See the chart below for a list of suitable circuit breakers that can be used. Follow the code and the circuit breaker manufacturers rating requirements regarding the size and temperature rating for wiring. Note that some pool equipment may be required to be connected to ground fault circuit
SUITABLE LISTED BREAKERS
Manufacturer | Single | Double | Twin | Quad | GFCB | Filler Plates |
|
BR | BR | BRD | BRD | GFCB | BRFP | ||
Murray | LX100FP | ||||||
Siemens | QP | QP | QT | QT | QPF | QF3 | |
Square D | HOM | HOM | HOMT | HOMT | HOM | HOMFP | |
Thomas & Betts | TB | TB | TBBD | TBBQ | GFB | ||
|
|
|
|
|
|
|
|
General Purpose Outlet
If desired, a duplex receptacle with weatherproof cover (supplied by installer) may be installed in the knockouts on the lower right side of the Aqua Logic enclosure. Per code, the receptacle should be a GFCI type. Alternatively, connect a standard receptacle to a GFCB.
Aqua Logic Control Power
The Aqua Logic requires 120VAC, 2A power to operate the control logic circuits and the chlorinator. This power should be connected to one of the circuit breakers.
!WARNING: 120VAC only (permanent damage if connected to 240V)
Factory
Prewired
120, 2VA
Field
Wired
11