![](/images/new-backgrounds/1116239/11623921x1.webp)
INDOOR HEATER
The design is also certified for indoor installation when equipped with the approved draft hood.
For Canada, indoor installation is restricted to an enclosure that is not occupied and does not directly communicate with occupied area. Refer to the latest edition of
Locate heater as close as practical to a chimney or gas vent. Heater must always be vented to the outside. See Vent Piping Section for venting details. Minimum allowable space is shown on the nameplate.
WARNING:
Indoor boilers require a drafthood that must be connected to a vent pipe and properly vented to the outside. Failure to follow this procedure can cause fire or fatal carbon monoxide poisioning.
OUTDOOR STACK / INDOOR STACK INSTALLATION
OUTDOOR KIT INCLUDES:
1- Draft hood, painted
1- Adapter plate
3- Mounting brackets
1- Top panel cover
2- 1 foot sections of metal tape
3- Screws
1- InstructionsClips
INDOOR KIT INCLUDES: 1- Draft hood, unpainted 1- Adapter plate
3- Mounting brackets
3- Screws
1- Instructions
Clips
INSTRUCTIONS:
1.Make sure that the gas and electric has been turned off to the unit.
2.Remove the "pagoda" top from the louvered top and discard. See Fig. 3.
3.Remove the louvered top and set aside, saving the four phillips screws for
4.Remove and discard the rain shield. See Fig. 4.
5.Install adapter plate on top of heater flue collector. See Fig. 5.
6.
11