NOTE: Do not use teflon tape on gas line pipe thread. A flexible sealant is recommended.
A minimum of 7" W.C. and a maximum of 14" W.C. upstream pressure under load, and no load conditions must be provided for natural gas or a minimum of 12" W.C. and a maximum of 14" for propane gas.
GAS PRESSURE REGULATOR
The gas pressure regulator is preset at 4" W. C. for natural gas, and 11" W. C. for propane gas. The pressure at the gas valve, taken with a manometer, should be about 3.7" W. C. natural gas (3.9" W.C. for Low NOx) and 10.5" W. C. propane gas. If an adjustment is needed, remove
seal and turn adjustment screw clockwise | to |
increase pressure or | to |
decrease pressure. |
|
ELECTRONIC IGNITION GAS VALVES-CONTINUED
Fig # 9328 | Fig # 9329 |
| Gas |
| Pressure |
| Adjustment |
Robertshaw 7200 | Robertshaw 7000 BDER |
Model 185 | Model |
Gas
Fig # 9327Pressure
Adjustment
Robertshaw 7000 DERHC
Model 405
PIPE SIZING FOR GAS CONNECTIONS
Fig. # 8149Fig. # 9365
ATMOSHPERIC | LOW NOx |
GAS PRESSURE ADJUSTMENT LOCATIONS
MILLIVOLT GAS VALVES
Gas
Pressure
Adjustment
Fig # 9263
Robertshaw 7000
Models 185 thru 405
ELECTRONIC IGNITION GAS VALVES
Gas
Pressure
Adjustment
Honeywell VR8304 |
|
Models 185 thru 405 | Fig # 9264 |
|
Low NOx units are not available in propane.
PLUMBING FOR WATER CONNECTIONS
LOCATION
The RP 2100 heater requires water flow and positive pressure to fire and operate properly. It must therefore be installed downstream of the discharge side of the filter pump. A typical installation is plumbed as follows:
1.The inlet side of the filter is plumbed directly to the discharge side of the filter pump;
2.The outlet side of the filter is then plumbed to the inlet of the heater; and
3.The outlet of the heater is plumbed to the return line to the pool or spa. The pump, filter and heater are thus plumbed in series.
16