Regency FG37-LPG Fluing Installation Precautions, Safety Precautions For The Installer

Models: FG37-NG FG37-LPG

1 32
Download 32 pages 56.78 Kb
Page 8
Image 8
FLUING

INSTALLATION

FLUING

The Regency Room Sealed System (Horizontal Termination Kit (946-110) and the Vertical Ter- mination with the Co-linear Flex System in combination with the REGENCY Room Sealed- Rear Freestanding Gas Stoves (FG37-NG and FG37-LPG) have been approved and listed as Room Sealed heater systems by Australian Gas Association.

The Horiz. Termination Kit (946-110) includes everything required for a straight through the wall installation, or add a 45o elbow for a corner installation.

IMPORTANT

Read all instructions carefully before starting the installation. Failure to follow these instruc- tions may create a fire or other safety hazard, and will void the warranty. Be sure to check the fluing and clearance to combustible require- ments on pages 6 to 9. Consult your local building codes before beginning installation.

The location of the termination cap must con- form to the requirements in the Exterior Flue Terminal Locations diagram on page 7.

FLUING

INSTALLATION

PRECAUTIONS

The Regency Room Sealed System and the Vertical Termination with the Co-linear Flex System are engineered products that have been designed and tested for use with the FG37-NG, and FG37-LPG. The Regency war- ranty will be voided and serious fire, health or other safety hazards may result from any of the following actions:

1)Installation of any damaged Room Sealed component

2)Unauthorized modification of the Room Sealed System

3)Installation of any component part not man- ufactured or approved by Regency Indus- tries Ltd.

4)Installation other than as instructed by Re- gency Industries Ltd.

Warning: Always maintain required clearances (air spaces) to nearby combustibles to prevent a fire haz- ard. Do not fill air spaces with insu- lation.

The minimum clearance requirements between the outer wall of the flue pipe and nearby combustible surfaces is 30mm. Be sure to check the flue termination clearance require- ments from decks, windows, soffits, gas reg- ulators, air supply inlets and public walkways as specified on page 7 and in your local building codes.

The gas appliance and flue system must be flued directly to the outside of the building, and never be at- tached to a chimney serving a sep- arate solid fuel or gas-burning ap- pliance.

Each Room Sealed gas appliance must use its own separate flue system. Common flue sys- tems are prohibited.

SAFETY

PRECAUTIONS FOR

THE INSTALLER

1)Wear gloves and safety glasses for pro- tection.

2)Exercise extreme caution when using lad- ders or on roof tops.

3)Be aware of electrical wiring locations in walls and ceilings.

PLANNING YOUR FLUING INSTALLATION

See page 7 for Exterior Flue Termination requirements.

When planning your installation, it will be nec- essary to select the proper length of flue pipe for your particular requirements. Determine the minimum clearance to combustibles from the rear of the unit to the wall. It is also important to note the wall thickness. Before cutting the flue hole through the wall ensure that ALL flue and termination clearances (see page 7) will be met.

NOTE: Ensure compliance with the outside flue terminal location before cutting hole as both dimensions must be met.

*If this is an outside corner, the minimum distance between the flue and the outside corner is 12" (30cm). See "F" on the diagram on page 7.

For corner installation, Restrictor must

For straight rear installation, Restric-

be set at 1-1/4" (32mm) open.

tor must be set at 1-1/8" (29mm) open.

8

FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater

Page 8
Image 8
Regency FG37-LPG, FG37-NG installation manual Fluing Installation Precautions, Safety Precautions For The Installer