Regency P36D-NG1 Rigid Pipe Venting, Venting Arrangements - Vertical Terminations, Gas Fireplaces

Models: P36-NG4 P36D-LP1 P36-LP4 P36D-NG1

1 8
Download 8 pages 39.45 Kb
Page 4
Image 4
Rigid Pipe Venting

P36 - P36D Gas Fireplace

Rigid Pipe Venting

Horizontal or Vertical Terminations

Gas Fireplaces

Gas Fireplaces

Vertical

Terminal

Storm Collar

Part # 953

Flashing

943 or 943S

Ceiling Firestop

(Part # 963)

Pipe Length

Vinyl Siding

Standoff (Optional)

Part #950

Vertical Horizontal Termination Cap (Part #946-523/P)

Wall Thimble

Part # 942

Adj.Pipe Length

11" - 14-5/8"

0

2

4

6

8

10

12

14

40

 

 

 

 

 

 

 

38

 

 

 

 

 

 

 

36

 

 

 

 

40ft.(12.2m)

 

 

34

 

 

 

 

 

 

 

 

 

 

 

Maximum:

 

 

90o Elbow

Pipe

Length

Alternate Horizontal

Termination Caps

32

30

Rigid Pipe Adapter

(Part# 510-994)

Alternate:

Horizontal

Riser Vent

Terminal

Part# 640-530/P

If required by the external termination location the listed alternate termination caps may be used. (Refer to Page 11)

Venting Arrangements - Vertical Terminations

Rigid Pipe System

(Propane & Natural Gas)

The P36 / P36D is approved for a maximum 40 ft. straight vertical, with Rigid Pipe vent systems for Propane and Natural Gas.

The lightly shaded area,

, in the diagram shows allowable venting

confi gurations with a maximum of two 45° elbows allowed.

The darker shaded area,

, in the diagram shows allowable venting

confi gurations using two 90° elbows.

Vent must be supported at offsets.

Horizontal sections must be supported every 3 feet

Firestops are required at each floor level and whenever passing through a wall.

Maintain clearances to combustible materials.

Minimum of 1’ pipe section between elbows.

Note: Must use optional flue adapter when using Rigid Pipe (Part

# 510-994).

38

 

28

 

 

 

26

 

 

 

24

 

 

(Feet)

22

 

 

20

 

 

Height

 

(8.2m)

 

 

Vertical

18

 

Maximum:27ft.

16

 

 

 

 

14

 

 

 

12

 

 

 

10

 

 

 

8

Minimum8’6”(2.6m)

Minimum10’6”(3.2m)

 

6

 

4

 

2

 

 

 

0

 

 

Minimum 12” (305mm)

Max. 10’ (3m)(centerline to centerline)

 

 

June 2007 Regency Product Specifications Book

Page 4
Image 4
Regency P36D-NG1 Rigid Pipe Venting, Venting Arrangements - Vertical Terminations, Alternate Horizontal Termination Caps