P36 - P36D Gas Fireplace
Venting Arrangements - Horizontal
Terminations
This diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90º elbow (two 45º elbows equal one 90º elbow).
The lightly shaded area, | , in the diagram shows allowable |
combinations when installing a P36 | |
The darker shaded area, | , in the diagram shows additional allowable |
combinations when installing a P36D.
Note: Must use optional flue adapter (Part #
•Maintain clearances to combustibles.
•Horizontal vent must be supported every 3 feet.
•Firestops are required at each fl oor level and whenever passing through a wall.
A vent guard may be required as per local codes, refer to page 11 for “Exterior Vent Termination Locations”.
Note: FPI Direct Vent System (Flex) is only approved for horizontal terminations.
Vertical Height (Feet)
0
18
16
14
12
10
8
6
4
2
0
Horizontal (Feet)
2 | 4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | 20 |
P36D ONLY
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
40 | June 2007 Regency Product Specifications Book |