1/4” per foot

Wall Thimble

downward slope

 

Vent Pipe

Ceiling

Board

Inspection

Inspection

Access Panel #1

Access Panel#2

Venting Through Closed Spaces

If the vent piping passes through a closed space, a minimum clearance of 8” (20 cm) when installed horizontally, 6” (15 cm) when installed vertically should be maintained between the vent pipe and combustibles and noncombustibles. Be sure to follow local codes.

For maintenance and inspection purposes, the following access panels are required.

Two (2) inspection access panels large enough to allow access for venting inspection. One (1) of these access panels should be close to where the vent pipe enters the ceiling. The other access panel should be near the vent termination.

A ventilation access panel with a 16 in2 (103 cm2) opening should be provided every 10 ft (3 m).

Exhaust

Flow

A

High Temp.

Sealant

B

Vent Adapter RTG20002B

Clamp

Collar

Vent Adapter

A UL 1738 approved stainless steel vent adapter is required for vent connection.

Read the following instructions before installation.

Test fit the adapter over the water

heater collar before proceeding. Adjust

clamp as needed.

With an alcohol wipe, clean inside

surface "A" of adapter and outside

surface of "B" of heater collar.

Tighten the clamp around the collar.

Inspect the inside of the adapter to verify that the collar and adapter are sealed. If more sealant is required, apply sealant to a flat tool, then spread around the collar edge on inside of adapter.

Ensure that the clamp does not interfere with the damper shaft.

NOTICE: Follow the vent adapter

Water Heater

Apply 1/4" (6 mm) wide bead of high

temperature silicone (500°F) (260°C)

around outside of heater collar "B".

Slide adapter end "A" down over heater

collar "B" as far as it will go.

manufacturer’s instructions

Draining the Condensate

In order to prevent condensate from draining back into the water heater, a condensate trap and drain must be installed in a horizontal vent section as close as practical to the water heater vent connection, uless the water heater is vented horizontally with a 1/4” per foot DOWNWARD slope towards the vent terminal as shown below.

Condensate is known to be acidic; refer to local, state (provincial) or federal codes for proper handling and discharge methods.

 

 

 

1/4” per foot downward slope

 

 

3” (8 cm) Clearance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3’

 

 

 

 

 

 

 

 

Support

 

 

 

(91 cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hanger

14

Max

 

 

 

Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adapter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 14
Image 14
Rheem AP13731 warranty Venting Through Closed Spaces, Vent Adapter, Draining the Condensate