Roberts Gorden 75, 100 Shelf Mounting and Suspension, Crush Hazard Use 3/8 threaded rod minimum

Models: 125 100 75

1 60
Download 60 pages 21.77 Kb
Page 18
Image 18
6.2 Shelf Mounting and Suspension

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL

6.2 Shelf Mounting and Suspension

Crush Hazard WARNING

Crush Hazard

Use 3/8" threaded rod minimum.

Failure to follow these instructions can result in death, injury or property damage.

Four suspension points (3/8" nuts) are located on the top of the heater. Drop rods must be 3/8" diameter mild steel minimum.

When handling or supporting the heater from below, ensure that the weight is taken at the support points. For typical suspension, See Page 10, Figure 5.

For typical shelf mounting on existing shelf, See Page 11, Figure 6.

The gas or electrical supply lines must not be used to support the heater.

Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater.

The heater must be installed in a location that is readily accessible for servicing.

The heater must be installed in accordance with clearances to combustibles as indicated on the wall tag and in this manual.

6.3 Wall Mounting

For typical suspension, See Page 11, Figure 7. Wall mounted heaters blowing parallel to the wall can only be installed with the service door away from the wall.

The wall mounting brackets must be attached to a suitable wall using all mounting holes. Screw sizes less than 3/8" may not be used. In order for the wall mounting brackets to adequately carry the weight of the heater, it must be installed according to best building practices.

Figure 5: Suspension Methods

10 of 47

Page 18
Image 18
Roberts Gorden 75, 100, 125 Shelf Mounting and Suspension, Crush Hazard Use 3/8 threaded rod minimum, Wall Mounting