Roberts Gorden 125, 75 Combustion Air Intake, Pipe, Heat Exchanger, Gas Line and Shut-off, Valves

Models: 125 100 75

1 60
Download 60 pages 21.77 Kb
Page 41
Image 41

 

SECTION 13: SERVICING

 

Combustion Air Intake

Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe,

Pipe

gaps in the sealed areas or corrosion.

 

The area must be free of dirt and dust.

 

Clean and reinstall as required.

 

See Page 19, Section 8

 

 

Heat Exchanger

Make sure there are no cracks.

 

Make sure there is no sagging, bending or distortion.

 

Clean or replace as required.

 

 

Gas Line and Shut-off

Check for gas leaks.

Valves

See Page 20, Section 9.

 

 

 

Burner Observation

Make sure it is clean and free of cracks or holes.

Window

Clean and replace as required.

 

 

 

Flue Blower Scroll, Wheel

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

and Motor

 

 

 

 

Inshot Burners and

Clear obstructions (even spider webs will cause problems).

Orifices

Carefully remove any dust and debris from the burner.

 

 

 

Direct-Spark Igniter

Replace if there are cracked ceramics, excessive carbon residue, or erosion

 

of the electrode.

 

The electrode gap should be 1/8" (3.2 mm).

 

 

Thermostat

There should be no exposed wire or damage to the device or wiring.

 

See Page 22, Section 10.

 

 

Suspension Points

Make sure the heater is hanging securely.

 

Look for signs of wear on the suspension materials or ceiling.

 

See Page 10, Figure 5.

 

 

Silicone Tubing

Ensure tight, secure fit on all pressure fittings at pressure switch,

 

burner partition, and blower outlet.

 

 

Gas Valve

Verify that cap covering pressure regulator adjustment screw is secure and

 

has not been tampered with.

 

Verify all wiring connections.

 

 

Condensate Drain

Flush drain and clear any obstructions.

(when installed)

 

 

 

 

Ductwork

Consult an indoor air quality professional for proper cleaning procedures.

 

 

Air Circulation Blower

For a complete inspection, refer to the manufacturers installation, operation

 

and service manual.

 

 

Wall Tag

If wall tag is present, make sure it is legible and accurate. Please contact

 

Roberts-Gordon LLC or your ROBERTS GORDON® independent distributor if

 

you need a wall tag. See Page 4, Section 2.1.

 

 

 

33 of 47

Page 41
Image 41
Roberts Gorden 125, 75 Combustion Air Intake, Pipe, Heat Exchanger, Gas Line and Shut-off, Valves, See Page 20, Section