Roberts Gorden 125, 75, 100 service manual General Technical Data Table, 45 of

Models: 125 100 75

1 60
Download 60 pages 21.77 Kb
Page 53
Image 53
16.2 General Technical Data Table

SECTION 16: SPECIFICATIONS

16.2 General Technical Data Table

 

Model

UHD[X][S] 75

UHD[X][S] 100

UHD[X][S] 125

 

 

 

 

 

Full Load Amps @ 120 V

A

1

2

2

 

 

 

 

 

Minimum Air Volume

CFM

850

950

1020

 

 

 

 

 

Temperature Rise @ Minimum Air Volume

°F (°C)

68 (37)

78 (43)

92 (51)

 

 

 

 

 

Heat Exchanger Pressure Drop @ Minimum Air Volume

in wc

0.06

0.05

0.06

 

 

 

 

 

Maximum Air Volume

CFM

2650

3660

4750

 

 

 

 

 

Temperature Rise @ Maximum Air Volume

°F (°C)

22 (12)

22 (12)

20 (11)

 

 

 

 

 

Heat Exchanger Pressure Drop @ Maximum Air Volume

in wc

0.36

0.55

0.98

 

 

 

 

 

Flue Size/Air Intake**

in (cm)

 

4 (10)-All models

 

 

 

 

 

 

Duct Size (Width)

in (cm)

16 3/4 (43)

21 3/4 (55)

21 3/4 (55)

 

 

 

 

 

Duct Size (Height)

in (cm)

15 7/8 (40)

15 7/8 (40)

15 7/8 (40)

 

 

 

 

 

Weight

lb (kg)

81 (36.7)

92 (41.7)

97 (44)

 

 

 

 

 

Recomended Mounting Height to Heater Base

ft (m)

12 (3.66)

20 (6.10)

20 (6.10)

 

 

 

 

 

*Do not exceed the maximum length of flue stated or heater may not operate properly.

16.3 Technical Data Table

 

Model

UHD[X][S] 75

UHD[X][S] 100

UHD[X][S] 125

 

 

 

 

 

Total Input

(Btu/h) x (1000)

75

100

125

 

 

 

 

 

Total Output

(Btu/h) x (1000)

61.5

82

102.5

 

 

 

 

 

Efficiency

%

 

82-All models

 

 

 

 

 

 

Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.

 

 

 

 

 

 

 

Burner Pressure

in. wc

3.5

2.6

3.3

 

 

 

 

 

LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.

 

 

 

 

 

 

 

Burner Pressure

in. wc

10.0

9.1

10.0

 

 

 

 

 