Roberts Gorden 75, 100 Pressure Switch, Ignition Control, Limit Switches, Removal and Replacement

Models: 125 100 75

1 60
Download 60 pages 21.77 Kb
Page 51
Image 51
15.6 Pressure Switch

SECTION 15: REPLACEMENT PARTS

15.6 Pressure Switch

Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are color coded for each pressure setting.

Carry out a start-up after working on or changing a pressure switch. See Page 26, Section 11.

MODEL

UHD[X][S] 75

UHD[X][S]100

UHD[X][S] 125

 

 

 

 

Pressure Switch Kit P/N

90439810

90439810

90439803

 

 

 

 

Color Code

black

black

gray

 

 

 

 

Set Point in wc

.35

.35

.41

 

 

 

 

Pressure Switch Snap Ring P/N

90439850

90439850

90439850

 

 

 

 

15.7 Ignition Control

The control mounts to the heat exchanger plate. Pull out ignition cable and wiring from board, noting their positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable and all other wiring.

15.8 Limit Switches

15.8.1 Removal and Replacement

1.Remove the electrical connections to the switch.

2.Unscrew the two screws securing the switch.

3.Fit a new switch with two screws.

4.Reconnect the electrical connections and test operation.

43 of 47

Page 51
Image 51
Roberts Gorden 75, 100, 125 service manual Pressure Switch, Ignition Control, Limit Switches, Removal and Replacement