SECTION 10: COMMISSIONING
SECTION 10: COMMISSIONING
Installation, service, commissioning and annual inspection of the heater must be done by a contractor qualified in the installation and service of
WARNING
Electrical Shock Hazard
Use extreme caution while commissioning.
Failure to follow these instructions can result in death or electrical shock.
10.1 Pre-Commission Checks
All
Ensure that the heater and all controls are suitable for the gas, pressure and electrical supply to which they are to be connected.
10.1.1 Louvres
Where fitted, the air delivery louvres need to be set during commissioning to give the required air distribution (optional vertical louvres).
WARNING
1.Check that all site wiring is connected in accordance with the appropriate wiring diagram on Page 14, Section 9.3.
2.Check the correct fuse size is fitted; See Page 13, Section 9.1.
10.1.3 Gas Supply
All aspects of the gas installation including the gas meter must be inspected, tested for soundness and purged in accordance with local and national codes. Ensure that the air is fully purged from the heater inlet pipe up to the main gas valve inlet test nipple.
10.1.4 Mechanical Checks
1.Check that the fan is free to run and
delivery louvres are turned to give required air deflection.
2.Check that the flue (and air intake for room sealed) is installed in accordance with these instructions and local regulations.
NOTE: The limit thermostat is sealed at the factory and is not adjustable.
10.2 Begin Commissioning
10.2.1 Before Operating the Heater
To ensure that all the controls are in safe working order, operate the heater for the first time with the isolating gas valve turned off.
1.Turn off the isolating gas valve.
2.Using the installed external control, turn on the
burner. The automatic sequence will now begin as described on Page 16, Figure 9.
There will be no ignition of the burner and lockout will occur, which proves the controls are operating correctly.
Cut Hazard
Turn off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe injury or product damage.
10.1.2 Electrical Checks
All
15