SECTION 13: CONVERSION BETWEEN GASES
SECTION 13: CONVERSION BETWEEN GASES 13.1 General
Conversion between gases will require a change of burner injectors and the gas valve
13.2 Burner Conversion
Conversion of the burner assembly from one gas to the other is the same for all types of heaters.
1.Remove the burner compartment cover as shown on Page 27, Section 15.2.
2.Remove the 4 screws holding the manifold and pull out the manifold.
3.Remove inshot burners by rotating them and sliding out the bracket.
4.Remove the main burner injectors.
5.Replace with the injectors for the new gas ensuring a gas tight seal.
6.Refit all components in reverse order.
13.3 Gas Valves
All gas valves used on the CTCU have pressure regulators that may be set to operate on natural gas or LPG.
Conversion is carried out by
21