SECTION 14: TROUBLESHOOTING 14.1 General

COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 14: TROUBLESHOOTING 14.1 General

Start WARNING

Explosion Hazard

Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.

Failure to follow these instructions can result in death, injury or property damage.

Start

Are gas & electrical

supplies on?

Yes

Is Red lockout

warning light on?

No

Does the fan run?

Yes

With external controls on, does the burner continue through the heating cycle?

Yes

Heater Operating

TROUBLESHOOT ENDS.

No

Yes

No

No

No

Turn on supplies.

Use 14.2 to test burner.

Use 14.5 to test fan.

Has burner “Locked Out”? No

The limit thermostat has

 

 

tripped.

No

Replace limit thermostat.

 

See Section 11.3.2.

 

 

Yes

Yes

 

 

Use 14.2 to test burner.

Replace axial fan.

 

 

If problems persist, contact

 

 

 

Roberts-Gordon Ltd. at

 

 

 

Tel: +44 (0)1902 498733

 

 

 

www.rg-inc.com

 

 

 

For your safety and optimum heater performance, use only ROBERTS GORDON® replacement parts.

Conduct Commissioning procedure as shown on Page 15, Section 10.