SECTION 14: TROUBLESHOOTING
14.4 Troubleshooting for Solenoid Valves
START
Is gas pressure at inlet of the valve correct for gas type?
Note pressure found.
Yes
Does gas pressure at outlet
of the valve rise when
valve turns on?
Yes
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
Yes
Valve Operating
TROUBLESHOOT ENDS.
No | Fault elsewhere. |
Valve or ignition control
No faulty. Replace with one of correct type.
Valve faulty.
No Replace with one of correct type.
If problems persist, contact
No | ||
Tel: +44 (0) 1902 498733 | ||
| ||
|
14.5 Troubleshooting for Main Fan
START
Does fan run
automatically? No
Yes
Does fan turn on and
off while burner is firing Yes continously?
No
Fan Operating
TROUBLESHOOT ENDS. No
Is power supply 230 V at | No | Is there 230 V between | Yes | Replace fan |
terminals T1 to N? | terminals L1 and N? | delay thermostat. |
Yes
Fan motor faulty.
Replace with correct type.
Replace fan
delay thermostat.
If problems persist, contact
Tel: +44 (0) 1902 498733
For your safety and optimum heater performance, use only genuine ROBERTS GORDON® replacement parts.
Conduct Commissioning procedure as shown on Page 15, Section 10.