Roberts Gorden CTCU 7, CTCU 27, CTCU 15, CTCU 11, CTCU 22 Flue Fan Vertical Installation

Models: CTCU 7 CTCU 22 CTCU 11 CTCU 15 CTCU CTCU 27

1 40
Download 40 pages 58.38 Kb
Page 35
Image 35
15.4 Flue Fan Vertical Installation

SECTION 15: REMOVAL AND REPLACEMENT PARTS

15.4 Flue Fan Vertical Installation

Air Intake

Adapter

Intake &

Exhaust Covers

Mounting Plate

to Vent Box

fixing screws

Manual background Gaskets

Manual background Vent Box

Mounting Plate

to Flue Fan

fixing screws

To remove the fan, remove 3 screws securing the fan and mounting plate to the vent box.

To remove the fan from the mounting plate, remove the 4 screws.

Refit in reverse order.

To change the flue and air intake orientation from back to top, remove the fan and mounting plate as above.

Remove intake and exhaust covers from top of the heater.

Intake &

Exhaust

Covers

Air Intake AdapterManual background

Rotate the fan, mounting plate and gasket clockwise until the flue adapter lines up with the top hole. Secure with 3 screws.

Gasket

Flexible Duct

Mounting Plate

to Vent Box

fixing screws

Remove the flexible duct from the air intake adapter on the back.

Remove the air intake adapter from the back of the heater and install in the appropriate hole on top. Reconnect the flexible duct.

Install intake and exhaust covers over the back holes.

Ensure sealed joints.

Ensure mounting plate orifice is clear and not obstructed.

MODEL

 

CTCU-7

CTCU-11

CTCU-15

CTCU-22

CTCU-27

CTCU-32

 

 

 

 

 

 

 

 

 

 

Fasco

Fasco

Fasco

Torin

Sit Controls

Sit Controls

Flue Fan

 

7021-11767

7021-11768

7021-11769

S6818

P1210838

P1210838

 

 

 

 

 

 

 

 

RG P/N

 

90710470

90710470

90710470

90710460

90710460

90710460

 

 

 

 

 

 

 

 

Air Plate

mm Ø

35

44

57

64

109.2

109.2

 

in Ø

1.38

1.75

2.25

2.50

4.3

4.3

 

 

 

 

 

 

 

 

RG P/N

 

11111210

11112210

11113210

11114210

11115210

11115210

 

 

 

 

 

 

 

 

IT IS IMPORTANT THAT ONLY THE CORRECT FLUE FAN SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.

Carry out a commission after working on or changing a flue fan. See Page 18, Section 11.