Rugged Outback RS416 manual DC Power Supply Wiring Examples, DC Power supply wiring examples

Models: RS416

1 36
Download 36 pages 56.83 Kb
Page 16
Image 16
4.2.2 DC Power Supply Wiring Examples
Figure 9:

4.2.2 DC Power Supply Wiring Examples

DC Power supply wiring examples

NOTES:

 

1.

88-300VDC rated equipment: A 300VDC appropriately rated circuit breaker must be

 

installed within 3m of unit.

2.

A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.

3.

Equipment must be installed according to the applicable country wiring codes.

4.

When equipped with two HI voltage power supplies, independent AC sources can be

 

used to power the product for greater redundancy. However, separate circuit breakers

 

must be installed and separately identified.

5.

When equipped with two DC voltage power supplies (88-300VDC rated); independent

 

DC sources may be used to power the product for greater redundancy. However,

 

separate circuit breakers must be installed and separately identified (as shown in the

 

above figure).

16

2008 RuggedCom Inc. All rights reserved

Rev104

Page 16
Image 16
Rugged Outback RS416 manual DC Power Supply Wiring Examples, DC Power supply wiring examples, installed within 3m of unit