5.4 Type Test Specifications
| 
 | Electrical Safety | 
 | Levels | 
 | 
 | Comments | |
| 
 | Dielectric Withstand | 
 | 2 kV rms for 1 minute | 
 | ANSI/IEEE C37.90 (1989) | ||
| 
 | 
 | 
 | IEC  | ||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | High Voltage Impulse | 
 | 5 kV peak | 
 | 
 | IEC  | |
| 
 | Insulation Resistance | 
 | 500 VDC for 1 minute | 
 | IEC  | ||
| 
 | Table 13: Type Test Specification - Electrical Safety | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | Electrical Environment | 
 | Levels | 
 | 
 | Comments | |
| 
 | High Frequency Disturbance | 
 | 2.5 kV @ 1MHz for 2s | 
 | ANSI/IEEE C37.90.1 | ||
| 
 | (Oscillatory) | 
 | 
 | IEC  | |||
| 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | IEC Surge | 
 | 4 kV / 2 kV | 
 | 
 | IEC  | |
| 
 | 
 | 
 | 
 | (Level 4) | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | IEC Fast Transient | 
 | 2 kV / 1 kV | 
 | 
 | IEC  | |
| 
 | 
 | 
 | 
 | (Level 4) | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | ANSI/IEEE Fast Transient | 
 | 4 kV | 
 | 
 | ANSI/IEEE C37.90.1 | |
| 
 | IEC Radiated RFI Immunity | 
 | 10 V/m | 
 | 
 | IEC  | |
| 
 | ANSI/IEEE Radiated RFI | 
 | 35 V/m | 
 | 
 | ANSI/IEEE C37.90.2 | |
| 
 | Immunity | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | ESD | 
 | 15 kV (air discharge) | 
 | IEC  | ||
| 
 | (Electrostatic Discharge) | 
 | 8 kV (contact) | 
 | (Level 4) | ||
| 
 | Table 14: Type Test Specification - Electrical Environment | 
 | 
 | ||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | Atmospheric Environment | 
 | Levels | 
 | 
 | 
 | Comments | 
| 
 | Temperature (Dry Cold) | 
 | 
 | 
 | IEC  | ||
| 
 | 
 | 
 | 
 | Test Ad: 16 hrs @  | |||
| 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | Temperature (Dry Heat) | 
 | 85°C | 
 | 
 | IEC  | |
| 
 | 
 | 
 | 
 | Test Bd: 16 hrs @ 85°C | |||
| 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | Humidity | 95% | 
 | 
 | IEC  | ||
| 
 | 
 | 
 | Test Db: 6 cycles, 55°C, 95% Humidity | ||||
| 
 | 
 | 
 | 
 | ||||
Table 15: Type Test Specification - Atmospheric Environment
33
|  2008 RuggedCom Inc. All rights reserved | Rev104 | 