5.4 Type Test Specifications

 

Electrical Safety

 

Levels

 

 

Comments

 

Dielectric Withstand

 

2 kV rms for 1 minute

 

ANSI/IEEE C37.90 (1989)

 

 

 

IEC 60255-5 (Section 6)

 

 

 

 

 

 

 

 

High Voltage Impulse

 

5 kV peak

 

 

IEC 60255-5 (Section 8)

 

Insulation Resistance

 

500 VDC for 1 minute

 

IEC 60255-5 (Section 6

 

Table 13: Type Test Specification - Electrical Safety

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Environment

 

Levels

 

 

Comments

 

High Frequency Disturbance

 

2.5 kV @ 1MHz for 2s

 

ANSI/IEEE C37.90.1

 

(Oscillatory)

 

 

IEC 60255-22-1

 

 

 

 

 

 

 

IEC Surge

 

4 kV / 2 kV

 

 

IEC 61000-4-5

 

 

 

 

(Level 4)

 

 

 

 

 

 

 

 

IEC Fast Transient

 

2 kV / 1 kV

 

 

IEC 61000-4-4

 

 

 

 

(Level 4)

 

 

 

 

 

 

 

 

ANSI/IEEE Fast Transient

 

4 kV

 

 

ANSI/IEEE C37.90.1

 

IEC Radiated RFI Immunity

 

10 V/m

 

 

IEC 61000-4-3

 

ANSI/IEEE Radiated RFI

 

35 V/m

 

 

ANSI/IEEE C37.90.2

 

Immunity

 

 

 

 

 

 

 

 

 

 

 

ESD

 

15 kV (air discharge)

 

IEC 61000-4-2

 

(Electrostatic Discharge)

 

8 kV (contact)

 

(Level 4)

 

Table 14: Type Test Specification - Electrical Environment

 

 

 

 

 

 

 

 

 

 

 

Atmospheric Environment

 

Levels

 

 

 

Comments

 

Temperature (Dry Cold)

 

-40°C

 

 

IEC 60068-2-1

 

 

 

 

Test Ad: 16 hrs @ -40°C

 

 

 

 

 

 

 

Temperature (Dry Heat)

 

85°C

 

 

IEC 60068-2-2

 

 

 

 

Test Bd: 16 hrs @ 85°C

 

 

 

 

 

 

 

Humidity

95%

 

 

IEC 60068-2-30

 

 

non-condensing

 

Test Db: 6 cycles, 55°C, 95% Humidity

 

 

 

 

Table 15: Type Test Specification - Atmospheric Environment