Samsung 3759 technical manual Installation, Indoor unit Example 4-way cassette type

Models: 3759

1 270
Download 270 pages 30.27 Kb
Page 237
Image 237

1-5. Installation

(1) Indoor unit (Example; 4-way cassette type)

1)Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit.

Note Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity. For this reason, before drilling the holes maintain the correct dimensions between the markings.

2)Insert bolt anchors, use existing ceiling supports or construct a suitable support as shown in figure.

IMPORTANT Ensure that the ceiling is strong enough to support the weight of the indoor unit. Before hanging the unit, test the strength of each attached suspension bolt.

If the length of suspension bolt is more than 1.5m, it is required to prevent vibration.

Concrete

Insert

Hole in anchor

Hole in plug

Suspension bolt(M8)-field supply

3)Install the suspension bolts depending on the ceiling type.

4)Screw eight nuts to the suspension bolts making space for

hanging the indoor unit.

IMPORTANT You must install the suspension bolts more than four when installing the indoor unit.

5) Hang the indoor unit to the suspension bolts between two nuts.

Note Piping must be laid and connected inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the piping into position for connection to the unit before placing the unit inside the ceiling.

Ceiling support

6)Screw the nuts to suspend the unit. Cut a pad stopper and place it on the bracket at this time.

7)Adjust the unit to the appropriate position considering the installation area for the front panel.

7-1 Place the pattern sheet on the indoor unit.

7-2 Adjust a space between the ceiling and the indoor unit by using the gauge of dimensions.

7-3 Fix the indoor unit securely after adjusting level of the unit by using a leveler.

7-4 Remove the pattern sheet, connect the other cables and install the front panel.

Note For installation of another indoor unit, refer to an appropriate installation manual.

Pad stopper

Bracket

Indoor Unit

20mm

 

Ceiling 17mm

Gauge of

Dimensions

V11

Page 237
Image 237
Samsung 3759 technical manual Installation, Indoor unit Example 4-way cassette type