IV. Outdoor unit
3. Functional parts and safety devices
IV
12
Item Code Name RVMH100GCM0
Motor output
Compressor safety OLP
Crank case heater
Fan motor
Safety thermostat
High pressure switch
Low pressure switch
Thermistor (discharge)
Thermistor (condenser center)
Thermistor (condenser outlet)
Thermistor (outdoor temperature)
Suction senser
Oil senser
Thermistor (fixed discharge)
Solenoid valve
(for compressor operation)
Solenoid valve
(for bypass of high temperature gas)
Solenoid valve (liquid injection)
Solenoid valve (for exhaust air)
Solenoid valve (for capacity control)
Solenoid valve (for capacity control)
4-way valve
Check valve
90W
OSME4506SRC
450W
150°C
100°C
ZRDT14MCE-TFD
4.2kW + 4.2kW
155
°C
70A
OFF : 30(±1)kg/cm
2
ON : 22(±1)kg/cm
2
OFF : 1.2(±0.2)kg/cm
2
ON : 2.2(±0.2)kg/cm
2
Model : 0166-01, Rt=150°C, 25°C=86
103AT (25°C=10k)
103AT (25°C=10k)
103AT (25°C=10k)
103AT (25°C=10k)
103AT (25°C=10k)
204CTB (25°C=200k)
Coil : Copeland (Part # 023-0028-03)
Body : EPV-1530D
Coil : Siginomiya
Body : NEV-603D
Coil : Siginomiya
Body : NEV-202D
-
-
Coil & Body : JAPAN RANCO VH-61100
Fujikoki (30kg/cm
2
)
-
-
CCH
Motor
HPS
LPS
DTS
CMS
COS
OATS
SUC.S
OIL.S
FDTS
PWM
HGBV
LBV
VBV
BV1
BV2
4-W/V
C/V
Compressor
Safety
devices
Temperature
sensor
Functional
parts
open temp.
trip current
model
output
on
off
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 12