Electrical work
• The electrical work should be performed by a specialist qualified for the work.
CAUTION • Avoid using
Wiring standard
ffAlways make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance with current local safety standards.
ffMake sure to install exclusive power supply(purchase separately).
fIfthe outdoor power supply has been selected, install circuit breaker (ELCB). (Purchased separately) ffMake sure to connect earth wire.
Type |
| Indoor unit | Indoor power (Indoor/outdoor unit power cable) |
| Outdoor unit | Outdoor power (Earth leakage circuit breaker) | |
|
| ||
| Power | 1Ph, 220~240V, 50Hz/60Hz | |
| Circuit breaker | 20A | |
Indoor/outdoor unit power cable | 1.0mm2 or more | ||
Outdoor unit power cable | 2.5mm2 or more | ||
Indoor/outdoor unit communication cable | 0.75mm2 or more |
Connecting procedure
1.After loosening the 4 screws(①) of
2.Connect the housings of communication cable(②) for an indoor unit and outdoor unit.
3.Fix the power connection cable and communication cable with a cable clamp.
4.After assembling the
Screw ①
SUPPORT-
INLET
COVER-PCB
Power terminal |
Earth plate |
Cable clamp |
Communication |
cable |
Power connection |
cable |
Housing ②
46