Preparing the installation
Selecting appropriate location for installation
Decide the installation location based on the following condition and obtain the user’s approval.
ffAvoid a place that may disturb your neighbor. Noise may occur from the outdoor unit and the discharged air may run into the neighborhood. (Be careful of the operation time in a residential area)
ffInstall the outdoor unit on a hard and even area that can support its weight. ffChoose a flat place that rainwater does not settle or leak.
ffChoose a place avoiding strong winds.
ffMaintain sufficient space for repairs and service.
ffChoose a place where you can easily connect the pipes and cables to the indoor unit.
ffMake sure that the condensed water dripping from the drain hose runs out properly and safely.
ffWhen installing the outdoor unit near seashore, make sure it is not directly exposed to sea breeze. If you can not find a adequate place without direct see breeze, protection wall should be constructed.
ffInstall the outdoor unit in a place (such as near buildings etc.) where it can be prevented from sea breeze which can damage the outdoor unit.
Outdoor unit
Sea breeze
Sea
Outdoor unit
Sea breeze
Sea
fIfyou cannot avoid installing the outdoor unit by the seashore, construct a protection wall around to block the sea breeze.
|
| Protection wall |
|
|
|
| Outdoor unit | • Protection wall should be constructed with a solid material | ||
|
|
|
|
|
| |||||
|
| Sea breeze |
|
|
|
|
| such as concrete to block the sea breeze and the height and | ||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| the width of the wall should be 1.5 times larger than the size | |||
|
|
|
|
|
|
|
|
|
| of the outdoor unit. Also, secure over 700mm between the |
| Sea |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| protection wall and the outdoor unit for exhausted air to |
|
|
|
|
|
|
|
|
|
| ventilate. |
ffInstall the outdoor unit in a place where water can drain smoothly. |
❋❋If you cannot find a place satisfying above conditions, please contact manufacturer. Make sure to clean the sea water and the dust on the outdoor unit heat exchanger and spread corrosion inhibitor on heat exchanger. (At least one time per one year.)
ffChoose a place where there is no direct sunlight.
ffChoose a place where it could not come into contact with snow and rain. ffChoose a place where flammable gas does not leak.
ffChoose a place where the indoor and outdoor unit can be connected with a pipe.
32