Installation method
Outdoor unit
When using the anchor bolt
Fix the unit on a flat, rigid floor using the anchor bolt. (Anchor bolt : M10 x 4 points - separately purchased)
Anchor bolt fixing dimensions
670mm
403mm | 427mm |
When using the rubber leg
Put the rubber leg to the outdoor unit leg.
Outdoor unit leg |
Rubber leg |
Installation procedures
1.The piping of this unit can be connected to the right, left, and rear side.
Holes for piping connection (4 points)
Protective piping cover
Piping
Drain hose
Protective piping cover
Drain hose
Piping
When the hole on the wall is lower than the hole for piping connection.
When the hole on the wall is higher than the hole for piping connection.
2.Open the front panel and separate it from the unit.
3.Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place.
❋❋When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant
If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the
CAUTION pipe length should be as short as possible (less than 25m).
38