Cutting/Extending the Piping

INSTALLING THE INDOOR UNIT

Cutting/Extending the Piping

5 metres(16ft. 5in) of piping is supplied with the air conditioner(Optional). This length can if necessary be:

Extended to a maximum of 20m (65ft. 7in).

Shortened as required

If more than 5m (16ft. 5in) of piping is required:

The assembly cable must also be extended

Refrigerant must be added to the circuit by an approved installer; otherwise, the indoor unit may freeze

1 Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder).

2If you wish to shorten the piping, cut it using a pipe cutter, taking care to

ensure that the cut edge remains at a 90° angle with the side of the pipe, and referring to the illustrations below for examples of edges cut correctly and incorrectly.

90O

Oblique

Rough

Burr

O

x

x

x

3 To prevent any gas from leaking out, remove all burrs at the cut end of the pipe, using a reamer.

4Slide a flare nut on to the pipe and modify the flare.

Pipe

Outer Diameter (D)

Depth (A)

Liquid refrigerant

6.35 mm(1/4˝)

1.3 mm(1/16˝)

Gas refrigerant

15.88 mm(5/8˝)

2.2 mm(1/8˝)

5Check that the flaring is correct, referring to the illustrations below for examples of incorrect flaring.

Inclined

Damaged Surface

Cracked

Uneven Thickness

6 Align the pipes to be connected and tighten the flare nuts first manually and then with a wrench, applying the following torque.

Pipe

Outer Diameter

Torque

Liquid refrigerant

6.35 mm(1/4˝)

160kg•cm(11.6ft•lb )

Gas refrigerant

15.88 mm(5/8˝)

700kg•cm(50.6ft•lb )

7For further details on how to connect up to the outdoor unit and purge the circuit, refer to page 43.