COMPLETING THE INSTALLATION
Purging the Connected Pipes
The outdoor unit is loaded with sufficient R410A refrigerant for a 24.6ft (7.5m) pipe You should purge the air in the indoor unit and in the pipe.
If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction of cooling capacity and malfunction.
Refrigerant for air purging is not charged in the outdoor unit. Use Vacuum Pump as seen in the picture.
1Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.
2Tighten the flare nut first with your hands, and then with a torque wrench, applying the following torque:
Outer Diameter | Torque |
1/4 inch (6.35mm) | 10.1~12.3ft•lb (140~170 kgf•cm) |
3/8 inch (9.52mm) | 18.1~20.3ft•lb (250~280 kgf•cm) |
1/2 inch (12.80mm) | 27.5~30.4ft•lb (380~420 kgf•cm) |
5/8 inch (15.88mm) | 31.8~34.7ft•lb (440~480 kgf•cm) |
3Connect the charging hose of the
The valve connection port of
4Open the valve of the low pressure side of manifold gauge counterclockwise.
5Purge the air in the connected pipes using the vacuum pump for about 10 minutes.
-Close the valve of the low pressure side of manifold gauge clockwise.
-Make sure that pressure gauge shows
This procedure is very important to avoid a gas leak.
-Turn off the vacuum pump.
-Remove the hose of the low pressure side of manifold gauge.
6Set a valve cork of liquid and gas service port to the open position.
7Mount the valve stem nuts and the service port cap to the valve, and tighten them at the torque of 13.2ft•lb (183kgf•cm) with a torque wrench.
8Check for a gas leak paying particular attention to the
9For further detailed information how to check the low pressure after installation, Please refer to the Service Manual.
Adding Refrigerant
You must add refrigerant if the pipe is longer than 24.6ft (7.5m).
If you use a |
| Then… | |
pipe… | AQV09J/AQV12J | AQV18J/AQV24J | |
| You can install 49.2ft(15m) | You can install 98.4ft(30m) of connecting | |
| of connecting pipe to the | ||
longer than | pipe to the maximum, and you should | ||
maximum, and you don’t | |||
24.6ft (7.5m) | charge 0.16oz(15g) of refrigerant R410A | ||
have to charge any additional | |||
| additionalyfor each extra feet(metre). | ||
| refrigerant. |
| |
shorter than | The purge time is normal. | The purge time is normal. | |
24.6ft (7.5m) |
Outdoor unit | Indoor unit |
Gas pipe side
Liquid pipe side
Vacuum
Pump
Valve stem
Stem cap
A
(gas)
| B |
5/16 inch (7.94mm) | (liquid) |
ENGLISH
Refer to the Service Manual for further details. | |
| |
|
|