Preparation

Step 1.1 Choosing the installation location

Overview of installation location requirements

CAUTION

Comply with the length and height limits described in the figure above.

Minimum clearances for the outdoor unit

Installation

 

 

100 mm or more

125 mm

 

125 mm

or more

 

or more

 

 

 

Drain hose hole

You can select the direction of

draining (left or right).

Maximum pipe height: 15 m

Maximum pipe length: 30 m

Make at least one round to reduce noise and vibration.

The actual units may look different from the images depicted here.

 

 

 

 

 

 

 

(Unit : m)

 

 

 

 

 

 

 

 

 

Model

 

Pipe length

Pipe height

 

 

 

 

 

 

 

Minimum

Maximum

Maximum

 

 

 

 

 

 

 

 

 

 

 

 

✴✴18✴✴

 

3

15

7

 

 

 

 

 

 

 

✴✴24✴✴

 

3

20

8

Outdoor

 

 

 

 

Make a U-trap (A) on the

Unit

 

 

 

 

pipe (which is connected to

 

 

 

 

 

CAUTION the indoor unit) at outer wall

 

 

 

 

 

Outer wall

 

 

 

 

and cut the bottom part of

Indoor

 

 

 

 

the insulation (about 10 mm)

 

 

 

 

to prevent rainwater from

 

 

 

 

Unit

 

 

 

 

getting inside through the

Cut insulation to have

insulation.

 

 

 

rainwater drained

 

 

 

 

 

Wall

 

 

 

 

Minimum clearance in mm

 

 

 

 

300

 

 

 

600

 

 

 

 

Air flow direction

 

 

 

Top view

Side view

 

When installing 1 outdoor unit

 

(6 cases)

 

 

 

 

(Unit: mm)

 

 

300

 

1500

300

 

 

2000

1500

 

150

600

 

 

500

300

 

 

300

 

 

 

 

 

 

 

1500

32English

Page 33
Image 33
Samsung AR18KQJSBWKNMG manual Preparation, Choosing the installation location, Minimum clearances for the outdoor unit