Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65 mm hole drilled in the wall, check the followings:

Wall

 

 

 

Indoor unit

 

 

 

Drain hose

 

 

 

 

The drain hose must NOT

The end of the drain hose

The drain hose must not

 

slant upwards.

must NOT be placed under

be bent.

 

 

water.

 

 

 

 

After completing the

 

 

 

installation of the drain

 

 

 

hose, pour water into

 

 

 

the drain pan to check

5cm

 

 

whether the hose is well

less

Ditch

 

drained.

Keep a clearance of at least

Do not place the end of the

 

 

5 cm between the end of the

drain hose in a hollow.

 

 

drain hose and the ground.

 

 

 

1) Correct connection

2) Incorrect connection

 

Drain hose

Pipe

 

 

 

 

 

 

 

 

 

Drain hose

Pipe

• Don’t tie drain hose to the assembly pipe which may lead to water leakage.

Drain hose installation

1.If necessary, connect the 2 meter extension drain hose to the drain hose.

2.If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.

3.Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain hose tightly with a clamp.

• If you do not use the other drain hose hole, block it with a rubber stopper.

4.When extending the Drain Hose, hold the end of Drain Hose and Extended Hose, rotate and insert the drain hose into Extended hose for 40~45 mm. Make sure the two hoses are firmly connected, there is no water leakage.

Drain hose hole

5.Connect the Drain Hose after using Foam Insulation to wrap the Extended Hose. Then, Use vinyl tape to wrap the each side of connection by 20 mm .

English-46

A3050 MG Model IB&IM_DB68-04542A_HP_EN.indd 46

2014/4/2 9:49:56

Page 46
Image 46
Samsung AR18HSFSEWKNMG, AR24HVFSEWKNMG, AR18HVFSEWKNMG manual Drain hose installation, English-46