11. PROCESSES AND FUNCTIONS
(2)Freeze Prevention
Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor
unit’s fan. | FREEZE | FREEZE |
| PREVENTION | PREVENTION |
MORE THAN 10 MINUTES | 6 MINUTES | 10 MINUTES | 6 MINUTES |
INDOOR COIL |
|
|
|
TEMPERATURE |
|
|
|
30°F |
|
| (THERMO ON) |
|
|
|
(THERMO OFF)
COMPRESSOR
ON
OFF
ON
OFF
ON
OUTDOOR FAN
ON
OFF
ON
OFF
ON
INDOOR FAN
SET SPEED
1029_X_S
Fig. 9
(3)Drain Pump Control
Drain pump operates when compressor starts to operate or when Float Switch turns off.
FLOAT SWITCH |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ON |
|
|
|
|
|
| OFF |
|
|
| ON |
|
| |||||
ON: low water level |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
OFF: high water level |
|
|
|
|
|
|
|
|
|
|
|
| 20 MINUTES |
|
|
|
|
|
|
| ||||
COMPRESSOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| OFF |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
| ON | |||||||||||||||||
|
| ON |
|
|
|
|
|
| ||||||||||||||||
| ON | OFF |
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
| OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
DRAIN PUMP |
|
|
|
|
|
|
| ON |
|
|
|
|
|
|
| |||||||||
| ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
OUTDOOR FAN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
| OFF |
|
|
|
| OFF |
|
|
|
| ON | |||||||||||
| ON |
|
|
|
|
|
| |||||||||||||||||
| ON |
|
|
|
|
|
|
| ||||||||||||||||
INDOOR FAN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| SET SPEED |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0609_X_S
Fig. 10
SM830078