11. PROCESSES AND FUNCTIONS

(2)Freeze Prevention

Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor

unit’s fan.

FREEZE

FREEZE

 

PREVENTION

PREVENTION

MORE THAN 10 MINUTES

6 MINUTES

10 MINUTES

6 MINUTES

INDOOR COIL

 

 

 

TEMPERATURE

 

 

 

30°F

 

 

(THERMO ON)

 

 

 

(THERMO OFF)

COMPRESSOR

ON

OFF

ON

OFF

ON

OUTDOOR FAN

ON

OFF

ON

OFF

ON

INDOOR FAN

SET SPEED

1029_X_S

Fig. 9

(3)Drain Pump Control

Drain pump operates when compressor starts to operate or when Float Switch turns off.

FLOAT SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

OFF

 

 

 

ON

 

 

ON: low water level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF: high water level

 

 

 

 

 

 

 

 

 

 

 

 

20 MINUTES

 

 

 

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

ON

 

 

 

 

 

 

 

ON

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN PUMP

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

OFF

 

 

 

 

ON

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

INDOOR FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET SPEED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0609_X_S

Fig. 10

SM830078

– 48 –