12.SERVICE PROCEDURES
3)Outdoor Unit does not Run.
A. Check COOL / FAN selector switch in the remote control unit.
•Is COOL/FAN selector switch NO set to COOL ?
Set to COOL.
0623_X_S
B. Check set temperature.
Try to lower set
temperature by Temperature setting button “COOLER”.
YES
•Set “Operation selector” switch to TEST in the indoor unit.
Outdoor unit runs.
Is room temperature too low ?
NO
•Try to run both indoor and outdoor units with another remote control unit.
OK
The other remote control unit is defective.
(Room sensor in the remote control unit is defective.)
0624_X_S
SM830078