Self-diagnostics Lamps
OPERATION (1) OPERATION lamp
TIMER (2) TIMER lamp
QUIET (3) QUIET lamp
OPERATION
<NOTE> | Since the indications cover various units, corresponding parts listed below may not be |
| present in some models. |
Indication on indoor unit | .... OFF |
|
| .... Blinking | .... ON (Illuminated) | ||||||||
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Quiet | Timer | Operation | Code | Diagnostics item |
|
|
|
| Diagnostics contents | ||||
(3) | (2) | (1) |
|
|
|
| |||||||
|
|
| S01 | Room temperature sensor failure | 1Sensor open circuit or short circuit |
|
|
| |||||
|
|
|
|
| 2Contact failure at connector or open circuit at terminal crimping location | ||||||||
|
|
| S02 | Indoor heat exchanger sensor failure | |||||||||
|
|
| detection only for the humidity sensor) |
|
| ||||||||
|
|
|
|
| 3Indoor/outdoor circuit board failure |
|
|
| |||||
|
|
| S03 | Humidity sensor failure |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S04 | Compressor temperature sensor failure | 1Sensor open circuit or short circuit |
|
|
| |||||
|
|
|
|
|
|
|
| ||||||
|
|
| S05 | Outdoor heat exchanger sensor failure | 2Contact failure at connector or open circuit at terminal crimping location | ||||||||
|
|
|
|
| 3Outdoor circuit board failure |
|
|
|
| ||||
|
|
| S06 | Outdoor air temperature sensor failure |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S07 | Outdoor electrical current detection | Outdoor circuit board failure |
|
|
|
|
| |||
|
|
| failure |
|
|
|
|
| |||||
|
|
| E01 | Indoor/outdoor communications failure | 3Blown fuse | 4Power relay failure | |||||||
|
|
| (serial communications) | 5Indoor or outdoor circuit board failure |
|
| |||||||
|
|
|
|
|
| ||||||||
|
|
| E02 | • HIC circuit failure | 1HIC or power Tr failure 2Outdoor fan does not turn. 3Instantaneous power outage | ||||||||
|
|
| 4Service valve not opened. | 5Outdoor fan blocked. | 6Continuous overload operation | ||||||||
|
|
| • Power Tr (transistor) circuit failure | ||||||||||
|
|
|
|
| 7Compressor failure 8Outdoor circuit board failure |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| E03 | Outdoor unit external ROM (OTP data) | 1External ROM data failure |
| 2Outdoor circuit board failure | ||||||
|
|
| failure |
| |||||||||
|
|
| E04 | Peak current | 1Instantaneous power outage | 2HIC or power transistor failure | |||||||
|
|
| 3Outdoor circuit board failure |
|
|
|
| ||||||
|
|
| E05 | • PAM circuit failure | 1Outdoor circuit board failure 2Outdoor power supply voltage failure | ||||||||
|
|
| • Active circuit failure | ||||||||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
| E06 | Compressor discharge overheat | 1Electric expansion valve failure | 2Capillaries choked | 3Shortage of refrigerant | ||||||
|
|
| prevention activated. | 4Continuous overload operation | 5Outdoor fan does not rotate 6Outdoor circuit board failure | ||||||||
|
|
| E07 | Indoor fan operating failure | 1Fan motor failure 2Contact failure at connector |
| 3Indoor circuit board failure | ||||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
| E08 | • |
|
| |||||||
|
|
| • Indoor | 2Outdoor circuit board failure |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
| E09 | 1Service valve not opened. |
| 2Shortage of refrigerant | |||||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
| E10 | DC compressor drive circuit failure | 1Open phase 2Outdoor circuit board failure |
|
| ||||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
| E11 | Outdoor fan operating failure | 1Fan motor failure 2Contact failure at connector |
| 3Outdoor circuit board failure | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| • Outdoor system communications failure |
|
|
|
|
|
|
|
|
|
|
|
| E12 | • Outdoor | 2Blown fuse | 3Power relay failure | 4Open phase | ||||||
|
|
| • OLR operation | ||||||||||
|
|
| 5Outdoor circuit board failure | 6Compressor failure |
| ||||||||
|
|
|
| • Outdoor power supply open phase |
|
|
|
|
|
|
|
|
|
|
|
|
| • Outdoor coil freezing |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
| E13 | 1Indoor fan system failure | 2Shortage of refrigerant | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
39