Industrial Control Transformers

Multiple Secondary

MULTIPLE SECONDARY

Designed to meet the needs for both 24 V control and 120 V control. Available in the 9070 Type T product line, with all the type T features.

Tapped Secondary D15: 24 V rated for 20% capacity and 120 V rated for 80% capacity when simultaneous loading, or 100% loading when 120 V only.

20% rating at 24 V or 100% rating at 120 V gives equal output current from the device.

VA

24 V amps

120 V amps

 

 

 

50

.416

.416

 

 

 

75

.625

.625

 

 

 

100

.833

.833

 

 

 

150

1.25

1.25

 

 

 

200

1.67

1.67

 

 

 

250

2.08

2.08

 

 

 

300

2.5

2.5

 

 

 

350

2.9

2.9

 

 

 

500

4.17

4.17

 

 

 

750

6.25

6.25

 

 

 

1000

8.3

8.3

 

 

 

1500

12.5

12.5

 

 

 

2000

16.7

16.7

 

 

 

3000

25

25

 

 

 

5000

41.7

41.7

 

 

 

Tapped Secondary D65: Both outputs fully rated for non-simultaneous loading, and simultaneous rated for any combination that does not exceed the nameplate VA rating.

Separate Windings Options: All voltage codes offer fully rated non-simultaneous loading, and simultaneous rated for any combination that does not exceed the nameplate VA rating.

Features of separate windings:

1.Allows two isolated control circuits, 24 V and 120 V, from the same device

2.Wire sizing for circuits for each voltage not highest current for common when simultaneous loading. (no common)

3.If a common is required, it can be obtained with a jumper kit.