Industrial Control Transformers
Type T MultiTap Transformers
11
08/2005 © 1999–2005 SchneiderEle ctric All Rights Reserved
120 Volt Secondary
Voltage and Connection Options
Voltage
Code
Voltages Connections
Primary Secondary Primary Secondary
D18 208/277/380 95/115
208: Connect to H1 and H2
277: Connect to H1 and H3
380: Connect to H1 and H4
95: Connect to X1 and X2
115: Connect to X1 and X3
D32
220/440/550
230/460/575
240/480/600
90/110
95/115
100/120
220 or 230 or 240:Connect to H1 and H2
440 or 460 or 480:Connect to H1 and H3
550 or 575 or 660:Connect to H1 and H4
90 or 95 or 100: Connect to X1 and X2
110 or 115 or 120:Connect to X1 and X3
D95
190/220/440
200/230/460
208/240/480
110
115
120
190 or 200 or 208:Connect to H1 and H2
220 or 230 or 240:Connect to H1 and H3
440 or 460 or 480:Connect to H1 and H4
110 or 115 or 120:Connect to X1 and X2
H1
X3 X2 X1
H3 H4H2
H1
X2 X1
H3 H4H2
Dimensions
VA Catalog
Number1Figure Acc.
Key
ABCEF Slots
UL CE IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
25 25 9070T25t1 II 3.09793.00762.58662.00512.50640.20 x 0.385 x 10
50 50 9070T50t1 II 3.34853.38862.89732.38612.81710.20 x 0.485 x 12
75 75 9070T75D32 1 II 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 0.20 x 0.48 5 x 12
75 75 9070T75t21 II 3.59913.75953.20812.88733.13800.20 x 0.385 x 10
100 100 9070T100t1 II 3.59913.75953.20812.88733.13800.20 x 0.385 x 10
150 150 9070T150D32 2 II 4.70 119 3.75 95 3.20 81 2.88 73 3.13 80 0.20 x 0.38 5 x 10
150 150 9070T150t21 II 3.59913.75953.20812.88733.13800.20 x 0.385 x 10
200 200 9070T200t2 II 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 0.20 x 0.38 5 x 10
250 160 9070T250D32 2 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 0.20 x 0.38 5 x 10
250 160 9070T250t22 II 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 0.20 x 0.38 5 x 10
300 200 9070T300D32 2 II 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 0.20 x 0.38 5 x 10
300 200 9070T300t22 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 0.20 x 0.38 5 x 10
350 250 9070T350t2 II 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 0.20 x 0.38 5 x 10
500 300 9070T500t2 II 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 0.28 x 0.56 7 x 14
750 500 9070T750t2 II 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111 0.28 x 0.56 7 x 14
1000 630 9070T1000t2 II 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148 0.28 x 0.56 7 x 14
1500 1000 9070T1500t2 II 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148 0.28 x 0.56 7 x 14
2000 1500 9070T2000t2 II 6.38 162 9.00 229 7.63 194 4.63 118 7.63 194 0.44 x 1.13 11 x 29
3000 2000 9070T3000t3 II 9.15 232 9.00 229 8.75 222 6.56 167 7.63 194 0.44 x 1.13 11 x 29
1Complete the catalog number by replacing the t with the correct Voltage Code from the “Voltage and Connection Options” table above.
2Complete the catalog number by replacing the t with Voltage Code D18 or D95 from the “Voltage and Connection Options” table above.
Figure 3
B
DA
E
F
C
DAB
FE
C
Figure 2Figure 1
C
B
DA
E
F