Industrial Control Transformers

Type T Transformers

Type T VA Ratings

UL, cUL, CSA and NOM VA

CE

Rating

VA Rating

 

 

25

25

 

 

50

50

 

 

75

75

 

 

100

100

 

 

150

150

 

 

200

200

 

 

250

160

 

 

300

200

 

 

350

250

 

 

500

300

 

 

750

500

 

 

1000

630

 

 

1500

1000

 

 

2000

1500

 

 

3000

2000

 

 

5000

3000

 

 

Type T Listings

Listing

File

VA Range

 

 

 

UL

E61239, Guide XPTQ2

25–5000

 

 

 

cUL

E61239

1500–5000

 

 

 

CSA

LR37055, Guide 184-N-90

25–1000

 

 

 

 

947923, EN 61 558/01.89 (TUV

 

 

ref: 00941-RAG/sg

25–200

 

E9371495E01)

 

 

 

 

 

9579078, EN 61 558/01.89 (TUV

 

EN

ref: 00941-RAG/sg

250–1000

 

E9471921E01)

 

 

 

 

 

9579078, EN 61 558/01.89 (TUV

 

 

ref: 00941-RAG/sg

1500–3000

 

E9471921.02E01)

 

 

 

 

TYPE T TRANSFORMERS

The Type T units are designed for the global market and are the best choice when size and cost are of concern. This is our most popular and complete offering of industrial control transformers. The following features are included:

50/60 Hz rated

Customer installed accessories (Finger-Safe covers, fuse blocks, fuse clips)

Type T transformers are designed with various temperature classes:

25–150 VA with a 55° C temperature rise, 105° C insulation

200–350 VA with a 80° C temperature rise, 130° C insulation

500–5000 VA with a 115° C temperature rise, 180° C insulation

Schneider Electric manufactures a wide variety of voltage combinations for control transformers. The voltage combinations are expressed as “Voltage Codes”, and are embedded within the catalog number of the transformer.

Standard codes are listed. If the voltage combination you need is not listed, please call your Schneider Electric distributor for assistance.

CE Marking

Industrial control transformers (ICTs) entering the European Union (EU) after January 1, 1997 are required by EU standards to have CE marking or Declaration of Conformity to CE. EU documentation requires compliance with specification EN 61 558 of the Low Voltage Directive. Type T ICTs from Schneider Electric comply with this specification and are third party tested to TÜV standards, which adhere to, and are accepted by, EU standards. A Declaration of Conformity for all Type T units is available upon request.

Because of different overload criteria in the CE specification,

Schneider Elecric dual rates these transformers for UL VA, cUL VA, CSA VA, NOM VA and CE VA ratings (see “Type T VA Ratings” table). Because they are widely used with control circuit panels, ICTs are also required to comply with EN 60 204 and EN 61 558 in these applications. The Type T transformer line complies with EN 60 204 when Fingersafe® covers are installed.

For more information regarding CE marking, please contact your local Schneider Electric field sales office.