Industrial Control Transformers

Fuse Protection

Primary Fusing to Meet NEC

Recommended Fuse Sizes for the PRIMARY (use class CC time delay fuses) to Meet NEC

 

 

120 Volts

 

 

240 Volts

 

 

480 Volts

 

 

600 Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VA

 

Fuse

Fuse

 

Fuse

Fuse

 

Fuse

Fuse

 

Fuse

Fuse

Primary

Rating

Primary

Rating

Primary

Rating

Primary

Rating

Rating with

Rating with

Rating with

Rating with

 

Current

Secondary

without

Current

Secondary

without

Current

Secondary

without

Current

Secondary

without

 

Amperes

Secondary

Amperes

Secondary

Amperes

Secondary

Amperes

Secondary

 

Protection

Protection

Protection

Protection

 

 

Protection

 

Protection

 

Protection

 

Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

0.21

1/2

1/2

0.10

1/4

1/4

0.05

1/8

1/8

0.04

1/10

1/10

 

 

 

 

 

 

 

 

 

 

 

 

 

50

0.41

1

1

0.21

1/2

1/2

0.10

2/10

2/10

0.08

2/10

2/10

 

 

 

 

 

 

 

 

 

 

 

 

 

75

0.63

1-1/2

1-1/2

0.31

6/10

6/10

0.16

3/10

3/10

0.13

3/10

3/10

 

 

 

 

 

 

 

 

 

 

 

 

 

100

0.83

2

2

0.42

1

1

0.21

1/2

1/2

0.17

4/10

4/10

 

 

 

 

 

 

 

 

 

 

 

 

 

150

1.25

3

3

0.63

1-1/2

1-1/2

0.31

6/10

6/10

0.25

6/10

6/10

 

 

 

 

 

 

 

 

 

 

 

 

 

200

1.67

4

4

0.83

2

2

0.42

1

1

0.33

8/10

8/10

 

 

 

 

 

 

 

 

 

 

 

 

 

250

2.08

5

3-2/10

1.04

2-1/2

2-1/2

0.52

1-1/2

1-1/4

0.42

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

300

2.50

6-1/4

4

1.25

3

3

0.63

2

1-1/2

0.50

1-1/8

1-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

350

2.92

7

4-1/2

1.46

3-1/2

3-1/2

0.73

2-1/2

1-8/10

0.58

1-4/10

1-4/10

 

 

 

 

 

 

 

 

 

 

 

 

 

500

4.17

10

6-1/4

2.08

5

3-2/10

1.04

3

2-1/2

0.83

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

750

6.25

15

10

3.13

7-1/2

5

1.56

3-1/2

3-1/2

1.25

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

8.33

20

12

4.17

10

6-1/4

2.08

5

3-2/10

1.67

4

4

 

 

 

 

 

 

 

 

 

 

 

 

 

1500

12.50

N/A

15

6.25

15

10

3.13

7-1/2

5

2.50

6-1/4

4

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

16.66

N/A

20

8.33

20

12

4.17

10

6 1/4

3.33

8

5

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

Recommended fuse sizes per NEC Article 450-3.

Transformers with primary only, select protection at 125%, if a standard size rating is not available, go to next higher rating.

Transformers with primary only and current rating is less than 9 A, select protection at no more than 167%.

Transformers with primary only and current rating is less than 2 A, select protection at no more than 300%.

Transformers with primary and secondary, select primary protection at not more than 250% and secondary at 125%. If a standard size rating is not available, go to next higher standard rating.

40

© 1999–2005 Schneider Electric All Rights Reserved

 

 

 

08/2005

Page 40
Image 40
Schneider Electric 9070 manual Primary Fusing to Meet NEC, Volts