Schneider Electric 9070 manual Application, Example of Series and Parallel Connections

Models: 9070

1 60
Download 60 pages 42.8 Kb
Page 55
Image 55

Industrial Control Transformers

Application

APPLICATION

In preparation for connecting power to the primary side of dual voltage single-phase transformers, it's necessary to first wire the two windings in either series or parallel to match the incoming voltage. An example of this is common transformers with a primary voltage description of 240 x 480. The windings are rated for the lower of the two voltages show on either side of the 'x'. Connecting the windings in series allows for the higher of the two voltages. Connecting the windings in parallel allows for the lower of the two voltages.

Example of Series and Parallel Connections

Jumper

H1 H3 H2 H4

X4

X2

X3

X1

Jumper

Series Connections

JumperJumper

H1

H3

H2

H4

X4

X2

X3

X1

Jumper

 

 

Jumper

Parallel Connections

NOTE: This diagram is for illustration purposes only. Actual units will have different combinations. See diagrams for actual connections.

55

08/2005

 

 

 

© 1999–2005 Schneider Electric All Rights Reserved

Page 55
Image 55
Schneider Electric 9070 manual Application, Example of Series and Parallel Connections