Schneider Electric EM3555 manual Event Bit Description

Models: EM3555

1 46
Download 46 pages 31.12 Kb
Page 44
Image 44

EM3555

ZL0093-0A

SunSpec Compliant Common and Meter Model Register Blocks

11/2011

 

 

Register

R/W

NV

Format

Units

Scale

Range

 

 

 

 

 

 

Events

 

 

 

 

 

 

40175

40176

R

NV ULong

Flags

 

 

 

 

 

 

 

 

 

 

 

End of SunSpec Block

40177

 

R

 

NV

 

UInt

 

 

0xFFFF

 

 

 

 

 

40178

 

R

 

NV

 

UInt

 

 

0x0000

 

 

 

 

 

 

 

 

 

 

SunSpec

Description

Name

 

 

 

M_Events

Bit Map. See M_EVENT_flags. 0 = no event

Event

 

Bit

Description

M_EVENT_Power_

0x00000004

Loss of power or phase

Failure

 

 

 

 

 

 

M_EVENT_Under_

0x00000008

Voltage below threshold

Voltage

 

 

(phase loss)

M_EVENT_Low_PF

0x00000010

Power factor below threshold

 

 

 

(can indicate misassociated

 

 

 

voltage and current inputs in

 

 

 

3-phase systems)

 

 

 

 

M_EVENT_Over_

 

0x00000020

Current input over threshold

Current

 

 

(out of measurement range)

 

 

 

 

M_EVENT_Over_

 

0x00000040

Voltage input over threshold

Voltage

 

 

(out of measurement range)

M_EVENT_

 

0x00000080

Sensor not connected (not

Missing_Sensor

 

 

supported)

 

 

 

 

M_EVENT_

 

0x00000100

Reserved for future SunSpec

Reserved1-8

 

to

use

 

 

0x00008000

 

M_EVENT_

 

0x7FFF000

Reserved for OEMs (not

OEM1-15

 

 

used)

 

 

 

 

 

C_SunSpec_DID = 0xFFFF

 

 

Uniquely identifies this as the last SunSpec block

 

C_SunSpec_Length = 0

 

Last block has no length

 

 

 

 

40

© 2011 Schneider Electric All Rights Reserved.

Page 44
Image 44
Schneider Electric EM3555 manual Event Bit Description