Schneider Electric EM3555 manual Quick Setup Instructions

Models: EM3555

1 46
Download 46 pages 31.12 Kb
Page 17
Image 17

ZL0093-0A

EM3555

11/2011

Quick Setup Instructions

 

 

QUICK SETUP INSTRUCTIONS

These instructions assume the meter is set to factory defaults. If it has been previously configured, all optional values should be checked.

1.

Press the + or button repeatedly until SETUP screen appears.

2.

Press

to the PASWD screen.

3.

Press

through the digits. Press + or to select the password (the default

 

is 00000). Exit the screen to the right.

4.

Press + or to select the parameter to configure.

5.

The first Setup screen is S COM (set RS-485 communications).

 

a. Press

to the ADDR screen and through the address digits. Press +

 

or

to select the Modbus address.

 

b. Press

to the BAUD screen. Press + or to select the baud rate.

 

c. Press

to the PAR screen. Press + or to select the parity.

 

d. Press

back to the S COM screen.

6.

Press to the S CT (Set Current Transducer) screen.

 

a. Press

to the CT V screen. Press + or to select the voltage mode

 

Current Transducer output voltage (default is 0.33).

 

b. Press

to the CT SZ screen and through the digits. Press + or to

 

select the CT size in amps.

 

c. Press

back to the S CT screen.

7.

Press to the S SYS (Set System) screen.

 

a. Press

to the SYSTM screen. Press + or to select the System Type

 

(see wiring diagrams).

 

b. Press

back to the S SYS screen.

8.

(Optional) Press to the S PT (Set Potential Transformer) screen. If PTs

 

are not used, then skip this step.

 

a.

to the RATIO screen and through the digits. Use the + or buttons

 

to select the Potential Transformer step down ratio.

 

b.

back to the S PT screen.

9.

to the S

V (Set System Voltage) screen.

 

a.

to the VLL (or VLN if system is 1L-1n) screen and through the digits.

 

Use the + or

buttons to select the Line to Line System Voltage.

 

b.

back to the S

V screen.

10.

Use the

to exit the setup screen and then SETUP.

11. Check that the wrench is not displayed on the LCD.

 

a. If the wrench is displayed, press + or to find the ALERT screen.

 

b. Press

through the screens to see which alert is on.

For full setup instructions, see the configuration instructions on the following pages.

© 2011 Schneider Electric All Rights Reserved.