Schneider Electric EM3555 manual Floating Point Data Per Phase

Models: EM3555

1 46
Download 46 pages 31.12 Kb
Page 39
Image 39

ZL0093-0A

EM3555

11/2011

Modbus Point Map

 

 

REGISTER

R/W

NV

Format

Units

 

Scale

Range

 

 

 

 

 

 

 

 

Floating Point Data: Per Phase

 

 

 

 

 

 

 

 

317/318

R

 

Float

kWh

 

 

 

319/320

R

 

Float

kWh

 

 

 

321/322

R

 

Float

kWh

 

 

 

323/324

R

 

Float

kWh

 

 

 

325/326

R

 

Float

kWh

 

 

 

327/328

R

 

Float

kWh

 

 

 

329/330

R

 

Float

kVARh

 

 

 

331/332

R

 

Float

kVARh

 

 

 

333/334

R

 

Float

kVARh

 

 

 

335/336

R

 

Float

kVARh

 

 

 

337/338

R

 

Float

kVARh

 

 

 

339/340

R

 

Float

kVARh

 

 

 

341/342

R

 

Float

kVARh

 

 

 

343/344

R

 

Float

kVARh

 

 

 

345/346

R

 

Float

kVARh

 

 

 

347/348

R

 

Float

kVARh

 

 

 

349/350

R

 

Float

kVARh

 

 

 

351/352

R

 

Float

kVARh

 

 

 

353/354

R

 

Float

kVAh

 

 

 

355/356

R

 

Float

kVAh

 

 

 

357/358

R

 

Float

kVAh

 

 

 

359/360

R

 

Float

kVAh

 

 

 

361/362

R

 

Float

kVAh

 

 

 

363/364

R

 

Float

kVAh

 

 

 

365/366

R

 

Float

kW

 

 

 

367/368

R

 

Float

kW

 

 

 

369/370

R

 

Float

kW

 

 

 

371/372

R

 

Float

kVAR

 

 

 

373/374

R

 

Float

kVAR

 

 

 

375/376

R

 

Float

kVAR

 

 

 

377/378

R

 

Float

kVA

 

 

 

379/380

R

 

Float

kVA

 

 

 

381/382

R

 

Float

kVA

 

 

 

 

 

 

 

 

 

 

 

Description

Accumulated Real Energy, Phase A

 

 

 

Accumulated Real Energy, Phase B

Import

 

Accumulated Real Energy, Phase C

 

Accumulated Real Energy (Ph)

Accumulated Real Energy, Phase A

 

 

 

 

Accumulated Real Energy, Phase B

Export

 

Accumulated Real Energy, Phase C

 

 

 

Accumulated Q1 Reactive Energy, Phase A

 

 

 

 

 

 

Accumulated Q1 Reactive Energy, Phase B

Quadrant 1

 

 

Accumulated Q1 Reactive Energy, Phase C

 

Import

 

Accumulated Q2 Reactive Energy, Phase A

 

 

 

 

 

Accumulated Q2 Reactive Energy, Phase B

Quadrant 2

 

 

Accumulated Q2 Reactive Energy, Phase C

 

 

Accumulated

Accumulated Q3 Reactive Energy, Phase A

 

 

Reactive Energy

 

 

(Qh)

Accumulated Q3 Reactive Energy, Phase B

Quadrant 3

 

 

Accumulated Q3 Reactive Energy, Phase C

 

Export

 

Accumulated Q4 Reactive Energy, Phase A

 

 

 

 

 

Accumulated Q4 Reactive Energy, Phase B

Quadrant 4

 

 

Accumulated Q4 Reactive Energy, Phase C

 

 

 

Accumulated Apparent Energy, Phase A

 

 

 

 

 

 

Accumulated Apparent Energy, Phase B

Import

 

Accumulated Apparent Energy, Phase C

 

Accumulated Apparent Energy (Sh)

Accumulated Apparent Energy, Phase A

 

 

 

 

Accumulated Apparent Energy, Phase B

Export

 

Accumulated Apparent Energy, Phase C

 

 

 

Real Power, Phase A

 

 

 

 

 

 

Real Power, Phase B

Real Power (P)

Real Power, Phase C

 

 

 

Reactive Power, Phase A

 

 

 

Reactive Power, Phase B

Reactive Power (Q)

Reactive Power, Phase C

 

 

 

Apparent Power, Phase A

 

 

 

Apparent Power, Phase B

Apparent Power (S)

Apparent Power, Phase C

 

 

 

 

 

 

 

© 2011 Schneider Electric All Rights Reserved.

35

Page 39
Image 39
Schneider Electric EM3555 manual Floating Point Data Per Phase