EXTENSION ANALOG OUTPUT

4.5.3Output signal setting

Set the output signals to be monitored. Set Pr. 306 to output the same signal from terminals AM0 and AM1 and Pr. 306 and Pr. 310 to output different signals. For details of signal definitions, refer to Pr. 54 and Pr. 158 of the inverter manual (applied).

Pr. 306/Pr. 310

Types of Monitor

Increments

Full-Scale Value

Setting

 

 

 

1

Output frequency

0.01Hz

Pr. 55

2

Output current

0.01A/0.1A *2

Pr. 56

3

Output voltage

0.1V

800V

5

Frequency setting

0.01Hz

Pr. 55

6

Running speed

1(r/min)

The value converted with the Pr. 37 value from Pr. 55.

8

Converter output voltage

0.1V

800V

9 *1

Regenerative brake duty

0.1%

Pr. 70

10

Electronic thermal relay

0.1%

Electronic thermal relay function operation level

function load factor

 

 

 

11

Output current peak value

0.01A/0.1A *2

Pr. 56

12

Converter output voltage

0.1V

800V

peak value

 

 

 

13

Input power

0.01kW/0.1kW *2

Rated inverter power × 2

14

Output power

0.01kW/0.1kW *2

Rated inverter power × 2

17

Load meter

0.1%

Pr. 56

21

Reference voltage output

24

Motor load factor

0.1%

200%

50

Power saving effect

Variable according to parameters

Inverter capacity

52

PID set point

0.1%

100%

53

PID process value

0.1%

100%

*1 Setting can be made only for the 75K(01800-EC, S75K-CH) or more.

*2 The setting depends on capacities. (55K (01160-EC, 55K-CH) or less/75K (01800-EC, S75K-CH) or more.)

18

Page 23
Image 23
Seagate FR-A7AY instruction manual Output signal setting, Types of Monitor Increments Full-Scale Value