Shinco Service Manual
F: Frequency keep unchanged
G:lower the present frequency on class( for example, from F4 to F3), and the maximum frequency is F3 in G area.
H:The compressor stops.
c. Frequency will change due to outdoor temperature, details see following fig.
4.3.2 Indoor heat exchanger anti-frozen
When indoor air sensor temperature is less than 3℃, the frequency will lower down to protect indoor heat exchanger. When indoor air sensor temperature is higher than 6℃ for more than 10 minutes, the air conditioner will return to former mode.
When indoor air sensor temperature is less than
4.3.3 Outdoor heat exchanger anti-overheated
When condenser temperature is higher than 54℃, the compressor frequency will be lowered down to protect the heat exchanger , and the outdoor fan runs in high speed. When condenser temperature lower down to 52℃, the compressor frequency rise up, and when the condenser temperature lower to 50℃ and keep for 5 minutes, and compressor frequency will rise to former value.
- 47 -