Shinco Service Manual
9 | DRIVER BOARD IS FAULT | P0 | DRIVER BOARD IS FAULT | DRIVER BOARD IS FAULT | |
10 | OCR TRIPED | P1 | 1、COMPRESSOR OCR IS OPEN CURCUIT | 1、CHANGE OCR OR COMPRESSOR | |
|
|
|
| 2、 CHECK IF THE OCR TEMPERATURE IS TOO HIGH AND OCR | 2、TURN OFF THE AIR CONDITIONER, AND RESTART |
|
|
|
| TRIPED | IT 2 HOUR LATER |
|
|
|
|
| 3、IF AIR CONDITIONER IS ON AND OFF |
|
|
|
|
| REGULARLY, CHECK OUTDOOR MOTOR OR MOTOR |
|
|
|
|
| CAPACITOR, THE OUTLET IS BLOCKED OR THE |
|
|
|
|
| CONDENSOR IS DIRTY |
|
|
|
|
| |
11 | POWER BOARD IS FAULT | P2 | OUTDOOR POWER BOARD IS FAULT | CHANGE THE POWER BOARD | |
12 | IPDU IS FAULT | P3 | |||
13 | INDOOR | UNIT DON’T MATCH | P4 | CHECK IF THE INDOOR UNIT MATCH OUTDOOR UINT | CHANGE WRONG UNIT。 |
| OUTDOOR UNIT |
| |||
|
|
|
| ||
|
|
|
|
| |
14 | ELECTRIC CURRENT IS TOO HIGH | P5 | 1、CHECK IF THE REFRIGERANT IS CHARGED TOO MUCH | 1、REGULATE THE QUANTITY OF REFRIGERANT | |
|
|
|
| 2、CHECK IF THE VOLTAGE IS TOO LOW, POWER WRINGIS TOO |
|
|
|
|
| THIN OR TOO LONG OR CONTACT BADLY | 2、UPDATING POWER SUPPLY, CHANG POWER WIRING |
|
|
|
| 3、 CHECK IF THE OUTLET IS BLOCKED OR THE CONDENSOR | 3、REMOVE OBSTACLE AROUND OUTDOOR UNIT OR |
|
|
|
| IS DIRTY | WASH THE CONDENDSOR |
|
|
|
| 4、CHECK THE OUTDOOR MOTOR WORK NORMALLY | 4、CHANGE OUTDOOR MOTOR OR MOTOR CAPACITOR |
|
|
|
|
| |
|
|
|
|
| |
15 | THE VOLTAGE IS NOT STABLE | P6 | CHECK THE POWER SUPPLY | RESTART THE AIR CONDITIONER | |
|
|
|
|
| |
16 | PFC FAULTY | P7 | OUTDOOR PFC BOARD IS FAULT | CHANGE PFC BOARD | |
17 | INDOOR | MOTOR FEEDBACK | P8 | ||
| FAULTY |
|
|
|
|
Note: The fault code doesn’t display directly, and it will display as following instruction:
Press the ON/OFF button 6 times within 7 seconds, there will be three DU sound on indoor unit, and the indoor unit will display the fault code.
- 58 -