Shinco Service Manual
KFR-50GWZ/BM、KFR-70GWZ/BM
Item | FAULT | CODE | CHECK POINT | COUNT MEASURE |
|
|
|
|
|
1 | INDOOR AIR SENSOR IS FAULTY | E1 | 1、CHECK THE SENSOR VALUE | CHANGE SENDOR |
|
| 2、INDOOR BOARD IS FAULT |
| |
|
|
|
| |
|
|
|
|
|
2 | INDOOR PIPE SENSOR IS FAULTY | E2 |
| CHANGE INDOOR BOARD |
|
|
|
| |
|
|
|
|
|
3 | INDOOR | E3 | ||
|
|
|
| |
|
|
|
|
|
4 | COMMUNICATION FAULT BETWEEN | E4 | 1、CHECK IF THE CONNECTING WIRING IS CONNECT WELL | 1、FIX THE WIRING AGAIN。 |
| INDOOR UNIT AND OUTDOOR UNIT |
| 2、TEST THE VOLTAGE VALUE BETWEEN L4 AND S, IF IT ‘S |
|
|
|
| CHANGE REGULARLY,THE SINGAL TRANSFERING BETWEEN |
|
|
|
| INDOOR AND OUTDOOR UNIT IS GOOD, |
|
|
|
| WHEN IT’S NO CHANGE | 2、CHANGE RELATE PCB BOARD |
|
|
| IF VALUE IS BELOW 14V, THE INDOOR PCB BOARD IS FAULT, |
|
|
|
| CHANGE IT. |
|
|
|
| IF VALUE IS OVER 14V,THE OUTDOOR PCB IS FAULTY |
|
|
|
| 3、CHECK IF THERE IS LED FLASHING ON THE OUTDOOR PCB |
|
|
|
| IF THERE IS NO FLASHING,CHECK VOLTAGE VALUE FROM |
|
|
|
| POWER BOARD TO PFC BOARD, BETWEEN ACL AND CAN ON PFC |
|
|
|
| BOARD |
|
|
|
| IF IT’S NOT 220V, CHANGE POWER BOARD |
|
|
|
| IF IT’S 220V,CHANGE PFC BOARD |
|
|
|
|
|
|
5 | DRIVER BOARD IS FAULT ) | E5 | DRIVER BOARD IS FAULT | DRIVER BOARD IS FAULT |
6 | OUTDOOR SENSOR IS FAULT | E6 | 1、CHECK THE SENDOR VALUE | CHANGE SENSOR |
|
|
| 2、POWER BOARD IS FAULT | CHANGE POWER BAORD。 |
|
|
|
|
|
7 | INDOOR MOTOR FAULTY | E7 | ||
|
|
|
| |
8 | COMMUNICATION SIGNAL IS | E8 | CHECK IF THE COMMUNICATION WIRING IS CONNECTED WELL. | FIX THE COMMUNICATION WELL |
| NOT GOOD |
| CHECK IF POWER BOARD OR DRIVER BOARD IS FAULT | CHANGE THE PCB BOARD |
|
|
|
|
|
- 57 -