Chapter 3 – Point Database

Descriptor

Address1

Application

Description

 

 

 

the space in cooling mode.

CLG FLOW MAX

32

All except 2597

The maximum amount of air in CFM (LPS) to be supplied to

 

 

 

the space in cooling mode.

HTG FLOW MIN

33

All except 2560, 2597

The minimum amount of air in CFM (LPS) to be supplied to

 

 

 

the space in heating mode.

HTG FLOW MAX

34

All except 2560, 2597

The maximum amount of air in CFM (LPS) to be supplied to

 

 

 

the space in heating mode.

AIR VOLUME

{35}2

All

Actual amount of air in CFM (LPS) currently passing through

 

 

 

the air velocity sensor.

FLOW COEFF

36

All

Calibration factor for the airflow sensor.

 

 

 

 

DO 3

{43}

All except

Digital output 3 controls a 24 Vac load with an ON or OFF

 

 

2562, 2564, 2566

status. If Motor 2 is enabled, DO 3 is coupled with DO 4 to

 

 

 

control an actuator.

HEAT STAGE 1

{43}

2562, 2564, 2566

This point is DO 3 in applications with electric reheat. This

 

 

 

digital output controls the contact for the first stage of heating

 

 

 

and has a status of ON or OFF.

DO 4

{44}

All except

Digital output 4 controls a 24 Vac load with an ON or OFF

 

 

2562, 2564, 2566

status. If Motor 2 is enabled, DO 4 is coupled with DO 3 to

 

 

 

control an actuator.

HEAT STAGE 2

{44}

2562, 2564, 2566

This point is DO 4 in applications with electric reheat. This

 

 

 

digital output controls the contact for the second stage of

 

 

 

heating and has a status of ON or OFF.

DO 5

{45}

2560, 2561, 2563,

Digital output 5 controls a 24 Vac load with an ON or OFF

 

 

2597

status. If Motor 3 is enabled, DO 5 is coupled with DO 6 to

 

 

 

control an actuator.

DO 5

{45}

2565, 2567

Digital output 5 controls a 24 Vac load with an ON or OFF

 

 

 

status.

HEAT STAGE 3

{45}2

2562, 2564, 2566

This point is a digital output used to control the contact for the

 

 

 

third stage of heating and has a status of ON or OFF.

FAN

{46}

2564, 2565, 2566,

This point is a digital output used to control the fan. ON

 

 

2567

indicates that the DO is energized; OFF indicates that the DO

 

 

 

is de-energized.

DMPR COMD

{48}

All except 2597

The value to which the damper motor is commanded in

 

 

 

percent of full travel.

MTR1 COMD

{48}

2597

The value to which the Motor 1 actuator is commanded in

 

 

 

percent of full travel.

DMPR POS

{49}

All except 2597

The current position of the damper motor in percent of full

 

 

 

travel. This value is calculated based on motor run time.

MTR1 POS

{49}

2597

The current position of Motor 1 in percent of full travel. This

 

 

 

value is calculated based on motor run time. See MTR1

 

 

 

TIMING.

MTR1 TIMING

51

All

The time required for the Motor 1 actuator to travel from full

 

 

 

closed to the full open position.

MTR2 COMD

{52}2

2560, 2561, 2597

The value to which the Motor 2 actuator is commanded in

 

 

 

percent of full travel (for use as an auxiliary slave point).

VLV COMD

{52}

2565, 2567

The value to which the valve actuator is commanded in

 

 

 

percent of full travel for applications using a water valve.

VLV1 COMD

{52}

2563

The value to which the valve 1 actuator is commanded in

 

 

 

percent of full travel for applications using a water valve.

MTR2 POS

{53}

2560, 2561, 2597

The current position of the Motor 2 actuator in percent of full

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

Siemens Industry, Inc.

 

 

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

 

 

4/20/2010

 

Page 26
Image 26
Siemens 125-5050 owner manual Descriptor Address1 Application Description