Chapter 3 Point Database
26
Siemens Industry, Inc.
BACnet ATEC Owner's Manaul
125-5050, Rev. AA
4/20/2010
Descriptor
Address1
Application
Description
the space in cooling mode.
CLG FLOW MAX 32 All
except
2597 The maximum amount of air in CFM (LPS) to be supplied to
the space in cooling mode.
HTG FLOW MIN 33 All
except
2560, 2597 The minimum amount of air in CFM (LPS) to be supplied to
the space in heating mode.
HTG FLOW MAX 34 All
except
2560, 2597 The maximum amount of air in CFM (LPS) to be supplied to
the space in heating mode.
AIR VOLUME {35}2 All Actual amount of air in CFM (LPS) currently passing through
the air velocity sensor.
FLOW COEFF 36 All Calibration factor for the airflow sensor.
DO 3 {43} All
except
2562, 2564, 2566
Digital output 3 controls a 24 Vac load with an ON or OFF
status. If Motor 2 is enabled, DO 3 is coupled with DO 4 to
control an actuator.
HEAT STAGE 1 {43} 2562, 2564, 2566 This point is DO 3 in applications with electric reheat. This
digital output controls the contact for the first stage of heating
and has a status of ON or OFF.
DO 4 {44} All
except
2562, 2564, 2566
Digital output 4 controls a 24 Vac load with an ON or OFF
status. If Motor 2 is enabled, DO 4 is coupled with DO 3 to
control an actuator.
HEAT STAGE 2 {44} 2562, 2564, 2566 This point is DO 4 in applications with electric reheat. This
digital output controls the contact for the second stage of
heating and has a status of ON or OFF.
DO 5 {45} 2560, 2561, 2563,
2597
Digital output 5 controls a 24 Vac load with an ON or OFF
status. If Motor 3 is enabled, DO 5 is coupled with DO 6 to
control an actuator.
DO 5 {45} 2565, 2567 Digital output 5 controls a 24 Vac load with an ON or OFF
status.
HEAT STAGE 3 {45}2 2562, 2564, 2566 This point is a digital output used to control the contact for the
third stage of heating and has a status of ON or OFF.
FAN {46} 2564, 2565, 2566,
2567
This point is a digital output used to control the fan. ON
indicates that the DO is energized; OFF indicates that the DO
is de-energized.
DMPR COMD {48} All
except
2597 The value to which the damper motor is commanded in
percent of full travel.
MTR1 COMD {48} 2597 The value to which the Motor 1 actuator is commanded in
percent of full travel.
DMPR POS {49} All
except
2597 The current position of the damper motor in percent of full
travel. This value is calculated based on motor run time.
MTR1 POS {49} 2597 The current position of Motor 1 in percent of full travel. This
value is calculated based on motor run time. See MTR1
TIMING.
MTR1 TIMING 51 All The time required for the Motor 1 actuator to travel from full
closed to the full open position.
MTR2 COMD {52}2 2560, 2561, 2597 The value to which the Motor 2 actuator is commanded in
percent of full travel (for use as an auxiliary slave point).
VLV COMD {52} 2565, 2567 The value to which the valve actuator is commanded in
percent of full travel for applications using a water valve.
VLV1 COMD {52} 2563 The value to which the valve 1 actuator is commanded in
percent of full travel for applications using a water valve.
MTR2 POS {53} 2560, 2561, 2597 The current position of the Motor 2 actuator in percent of full