Chapter 2 – Applications

See the following figure.

Fan Operation

The fan turns on when heating is required.

[insert TEC2566CD]

Application 2867 VAV Parallel Fan Powered with Hot Water Reheat

In Application 2867, the controller modulates the supply air damper of the terminal box for cooling and modulates a hot water valve for heating. When in heating, the terminal box either maintains minimum airflow or modulates the supply air damper. Application 2867 has a parallel fan that re-circulates the room air. In order for the terminal box to work properly, the central air-handling unit must provide supply air.

See the following figure.

 