Siemens pa module p03-01 manual Acquisition and Storage of Curve Values, Designing Curve Displays

Models: pa module p03-01

1 42
Download 42 pages 52.97 Kb
Page 6
Image 6

Industry Sector, IA&DT

Acquisition and Storage of Curve Values

For the displayed course to reflect the actual course, the sampling rate of the process value has to correspond at least to twice the change frequency of the process value. In most cases, this requirement can be met with cyclical acquisition every 1s [2].

In PCS 7, the sampling rate corresponds to the acquisition cycle of a process value. As long as a process value is not archive, only the pre-history of the process value can be displayed. By archiving a process value (refer to chapter P02-03) the history can be displayed also, since archive variables are resorted to.

When curves are displayed, the pre-history differs from the history as shown in Table 1.

Table 1: Visible Differences between Prehistory and History [2]

 

Prehistory

History

 

 

 

Position of the time span

Always relative to the

Through an absolute point

shown in the curve field

present

in time and a selected time

 

 

span or through two

 

 

absolute points in time

 

 

 

Labeling of the time axis

Relative time indications; if

Absolute time indications

 

needed, can be switched to

can be switched to time

 

absolute time indication

indications relative to a

 

 

defined point in time of an

 

 

event

 

 

 

Updates

Curve is updated during the

Curve does not change

 

display whereby all curve

 

 

points are shifted

 

 

 

 

Value axis

The value axis is usually

The value axis is located on

 

located at the point in time of

the left margin of the display

 

the present (at the right

 

 

margin of the display)

 

 

 

 

Designing Curve Displays

In [2], guidelines for designing curve displays are provided. PCS 7 implements the basic design details by default; for that reason, they are described here only briefly. There are design rules, however, that you can implement yourself by means of the settings at OS engineering. To do this in a specific way, a few details are introduced here.

The curve display is displayed in the working area of the display area (refer to P02-01). It consists of the title field, the curve labeling field, and the curve field. The title field should contain the information for the unambiguous assignment to the process environment. In the curve labeling field, it should be possible to read off the relationship of displayed the curve and the process value. The curve display field is used to display the curve and should be as large as possible. To implement the curve display field, the following information is provided.

To facilitate reading off the values, grid lines have to be available. The value axis in this case should display several lines as an extension of the scale marks, and the time axis several lines according to the current time grid. The number of grid lines should be low and optically remain in the background. To this end, they should not be shown in color or blue. Reading rulers can provide additional support.

SCE Training Curriculum

Page 6 of 42

To be used only at Educational and R&D Facilities

PA Module P03-01, Edition 09/2013

 

Unrestricted / © Siemens AG 2013. All Rights Reserved

P03-01_AdvancedLayout_R1309_en.doc

 

 

 

 

 

Page 6
Image 6
Siemens pa module p03-01 manual Acquisition and Storage of Curve Values, Designing Curve Displays, Industry Sector, IA&DT