Appendix A: Technical Data

Interfaces

USB

1 x front panel *), 1 x rear panel (internal connection to the computing unit)

Safety

Protection class

 

Conforms to VDE 0106 T1: 1982 (IEC 536)

 

Degree of protection

a.

with screw fixing

IP 54

 

 

b.

with clamp fixing, gasket and inserted rubber plug for

IP 65

 

 

 

USB interface

 

 

 

c.

touchscreen version without front-side USB interface,

NEMA 4 and IP 65,

 

 

with clamp fixing and gasket

indoor use only

 

 

 

Safety regulations

 

IEC, corresponding to DIN VDE 0805/11.93

Electromagnetic compatibility

 

CE, EN 50081-2, EN 50081 (EN 55022), IEC 1000-4-2,

 

 

 

IEC 1000-4-4, IEC 1000-4-5, ENV 50140, ENV 50204

Certification

 

CE, UL 508/CSA, FCC

 

Power supply

 

Typically approx. 13 W, max. approx. 21 W

 

Oscillation load in operation

 

10 to58 Hz: 0.075 mm, 58 to 500 Hz: 1 g

 

tested to

 

DIN IEC 68-2-6

 

Shock load in operation

 

50 m/s2, 30 ms, 100 shocks

 

tested to

 

DIN IEC 68-2-29

 

Ambient conditions

 

 

 

Heat dissipation

 

by natural convection

 

Temperature limit values

 

5°C ... 45°C

 

±

in operation

 

 

±

in storage/transport

 

±20°C ... 60°C

 

tested to

 

DIN EN 60068-2-2: 1994, DIN IEC 68-2-1, DIN IEC 68-2-14

Limit values for rel. humidity

 

5 ... 80 % at 25 °C

 

±

in operation

 

 

±

in storage/transport

 

5 ... 95 % at 25 °C

 

tested to

 

DIN IEC 68-2-3, DIN IEC 68-2-30, DIN IEC 68-2-56

Temperature variation

 

max. 10 K/h

 

Mositure condensation

 

not permissible

 

Intake air

 

without aggressive gases

 

Warranty period

 

24 months

 

___________________________________________________________________

*) not for NEMA-standard versions (see ªDegree of protectionº, version c.)

A-2

SIMATIC Panel PC 670 / 870 Operating Unit, Equipment Manual

Edition 07/01

Page 40
Image 40
Siemens PC 870 manual Appendix a Technical Data