Configuration / diagnostics using remote mechanisms
6.3 Configuration using Web Based Management (WBM) and Command Line Interface (CLI)
SCALANCE X-200
Operating Instructions, 12/2011, A5E00349864-19 241
Variable Access rights Description
snX200FaultState Read and write Displays the error status of the device. Possible values:
1 No error
2 Error
snX200FaultValue Read only Errors are assigned an ascending index according to the order in
which they occur. This 4-byte variable specifies the index.
snX200RmState Read only Indicates whether the redundancy manager is active or passive.
Possible values:
1 The redundancy manager is passive. The IE Switch X-200 is
operating as redundancy manager and has opened the ring. In
other words, the bus with the IE Switches X-200 connected to it is
operating correctly. The "Passive" status is also shown when the
redundancy manager mode is disabled.
2 The redundancy manager is active. The IE Switch X-200 is
operating as redundancy manager and has closed the ring. In
other words, the bus with the IE Switches X-200 connected to it is
interrupted (fault). The redundancy manager switches through the
connection between the ring ports and thus restores a functioning
bus configuration.
snX200RmStateChanges Read only Indicates how often the redundancy manager was switched to
"active".
snBootStrapVersion Read only The firmware version of the bootloader in the format major.minor.
snHwVersion Read only The hardware version of the system in the format major.minor.
snInfoSerialNr Read only The serial number of the product.
snMacAddressBase Read only The MAC address of the IE Switch X-200.
snSwVersion Read only The software version of the system.
snInfoMLFB Read only The MLFB number of the device.
snX200PowerSupplyState Read only State of the redundant power supply:
1 Redundant supply
2 No redundant supply
Note:
The following devices do not have a redundant power supply:
- SCALANCE X204 IRT PRO
- SCALANCE X202-2P IRT
- SCALANCE X201-3P IRT
- SCALANCE X201-3P IRT PRO
SnX200RmMode Read only The redundancy manager mode
1 The IE Switch X-200 is redundancy manager.
2 The IE Switch X-200 is not redundancy manager.