HOST COMMAND SET REFERENCE
UNILINK HOST
ADAPTER5–17
USER MANUAL
5.3.8
Read Adapter Diagnostics — 08
The READ ADAPTER DIAGNOSTICS command returns statistics for the
entire
network related to the issuing HIU. W
ith the exception of
the number of
I–Frames transmitted to and from the secondaries and the number of various
commands
issued to the HIU, the
statistics counters do not represent an exact
count of the events and are intended only to show trends that may indicate
problems. These counters are not updated when they reach their maximum
value of FFFF. The host computer must issue this command with the reset
counter
code set to reset these counters.
Command:
08
(rr)
Response:
08
(aaaa bbbb cccc dddd eeee ffff gggg hhhh iiii jjjj kkkk
llll mmmm nnnn oooo pppp qqqq rrrr ssssssss)
Usage: PERFORMANCE
Modes:
MHIU/EHA, HIU/EHA, MHIU, HIU
Parameters:
rr The reset statistics counters code. This parameter was added to
the original TIWAY I Host Adapter command to allow the
counters
to be reset.
00 = Return the statistics counters, but do not reset them.
01 = Reset the statistics counters and do not return any counts.
aaaa The number of invalid commands received from the host
computer. Invalid commands do not include commands that are
rejected
due to transmission errors, such as a bad checksum.
bbbb The number of valid SEND NETWORK DATA commands
processed.
cccc The
number of valid BROADCAST NETWORK DA
TA
commands
processed.
dddd The
number of valid POLL SECONDARY commands processed.
eeee The number of valid CONNECT SECONDARIES commands
processed.
ffff The
number of valid DISCONNECT SECONDARIES
commands
processed.
gggg The number of valid READ SECONDARY LOG commands
processed.
hhhh The number of valid READ SECONDARY DIAGNOSTICS
commands
processed.
iiii The number of valid READ ADAPTER DIAGNOSTICS
commands
processed.