CONFIGURING THE HOST COMPUTER PORT
UNILINK HOST
ADAPTER 3–12
USER MANUAL
The host port communication parameters are configured with two 10-position
dipswitches
located at the front of
the adapter as shown in Figure 3–3. T
o select
NITP as the operating protocol, set position 1 of Dipswitch 1 up as shown in
Figure
3–10.
12345678910
U
P
DIPSWITCH 1
HOST COMMAND
12345678910
U
P
DIPSWITCH 2
MSB LSB
UP = SYNCHRONOUS
DOWN = ASYNCHRONOUS
UP = FULL DUPLEX
DOWN = HALF DUPLEX
UP = TEST MODE
DOWN = RUN MODE
UP = HIU/EHA &
DOWN = MHIU/EHA
HOST PORT BAUD RATE
UP = EVEN PARITY
DOWN = ODD PARITY
UP = PARITY ENABLED
DOWN = PARITY DISABLED
HOST PORT
HOST PORT
HOST PORT
HOST PORT
TIMEOUT
IO LOOP TEST
UP=NTP
UP DOWN
KEY
Figure 3–10 NITP Dipswitch SettingsNOTE
The host port parameters specify the physical layerprotocol parameters and do not imply that the datalink protocols can be either asynchronous orsynchronous. Both the BDLC and NITP protocols areasynchronous data link layer protocols.